56
Selectronic Australia
Rev 41 - Dec 2022
Service
Inverter Start-Up Problems
SP PRO will not start
If the indicators remain dark (not including the three blue LEDs along the top) when the SP PRO is switched on,
then it is likely that DC battery power is not present. Check all the main battery wiring and terminals. Also check
that the main battery fuse or circuit breaker is closed. Retry the start-up procedure and if the problem continues
contact the installer for further instructions.
Resetting the Inverter
The following procedure will reset the inverter, with or without restoring factory defaults
Set SP PRO in idle mode with a long press of the ON button (On LED flashing Yellow)
•
To reset inverter without restoring factory defaults, press and hold buttons
B
as shown below. All indicators
will go off. Release buttons
B
and inverter will reset.
•
To reset inverter and restore factory defaults, press and hold buttons
B
as shown below. All indicators will go
off. Whilst continuing to hold
B
, press
C
to select from following options:
Press
C
once. All LEDS green = Reset to factory defaults.
Press
C
twice. All LEDS OFF = Reset without setting factory defaults.
Release all buttons, wait 10 sec until display is stable. Your reset, with or without restoring factory
defaults is complete.
The SP PRO will not run after restoring factory defaults as it is not configured. SP LINK must be used to
send a configuration to the SP PRO before it will run.
It is recommended that the SP PRO be reset to factory defaults and then reconfigured after a firmware
update. This will ensure a clean configuration.
All inverters in a Powerchain system must be reset to factory defaults before inverter assignment and
configuration.
It is recommended that the SP PRO configuration is saved to a site file in SP LINK before restoring factory
defaults.
Troubleshooting