background image

11

Use a  non-hardening high-temperature silicone sealant (500°F)  to seal
around the horizontal chimney length where it enters through the
exterior of the Wall Thimble or  the concrete wall.

Twist lock a 12" section into the Female Coupler beneath the Support
Plate.  Twist lock the Tee Plug into the bottom of the section. You can
substitute an Insulated Tee Plug (1TPI) for the 12" section.

Chimney Lengths above the Insulated Tee are simply stacked on and
locked with a 1/8 clockwise turn.  It is highly recommended to secure all
exterior chimney joints with Locking Bands (SLB).
For lateral stability of the chimney above the Wall Support, a Wall Band
must be installed along an outside wall.  Install the first Wall Band
midway up the first Chimney Length above the Insulated Tee. Any
additional Wall Bands are to be installed at 8 foot intervals above this
point.

The nut and bolt supplied will fasten the band around the chimney.

Wall Band

Figure 18

Securely fasten the Wall Band around the chimney with the supplied nut
and bolt.  Check for clearances and plumb as you fasten the Wall Bands
to the wall.  Use a level against the chimney section at each support stage
to keep the assembly plumb.

Secure the Wall Band bracket to the wall using two 6d (2”) spiral nails
or #8 x 2" wood screws or longer  if required through the pre-drilled holes
(see Figure 18).  For concrete or brick veneer walls use suitable masonry
fasteners.

ADJUSTABLE INTERMEDIATE

WALL SUPPORT (AIWS)

If the total chimney height exceeds the Wall Support (AWS)  limitations

an Adjustable Intermediate Wall Support must be installed.  Use of an

AIWS will support an additional 38ft. of chimney.  The AIWS is

adjustable from 2" to 2-1/2" only from the vertical wall.  Slide the

assembled Intermediate Wall Support over the protruding length of

chimney.  Fasten the Intermediate Wall Support to the wall using four

1/4” by 2” wood screws through the pre-punched slots in each bracket.

Install the draw band around the protruding chimney length securely

against the support plate.  Install four stainless steel sheet metal screws

firmly into the outer casing of the chimney, through the pre-punched

holes in the draw band.  Cover the heads of the screws with a non-

hardening waterproof caulking.

NOTE:  If a greater adjustment is required, such as to clear an overhang,

the WS Wall Support must be installed.  This support is ordered
separately.

NOTE:  

Interior chimneys installed with a Wall Support must use a

Firestop Radiation Shield (FRS) in place of Wall Bands if extending

through floor/ceiling penetrations and an Attic Insulation Shield when

passing through an unoccupied attic space.

If roof overhangs the wall of the structure so that passage of the

chimney is obstructed, it is necessary to cut an opening in the

overhang.  Allow the minimum 2" air space clearance to combustible.

To find the exact spot where the chimney will pass through the

overhang, drop a plumb line from the underside to the outer edge of the

leveled chimney length.  Mark 5 or 6 points to give an outline of the hole.

Keep in mind the 2" clearance to the chimney outer surface.  Install an

Attic Insulation Shield if space permits on the under side of the

overhang.  If it is not possible, the overhang can be enclosed and a

Rafter Radiation Shield installed at the roof level and a Finishing Plate

on the underside.  If the Attic is open to the overhang, close off the

access with suitable building materials ensuring that a 2" air space

clearance is maintained.   From above, install the Roof Flashing and

Storm Collar by following the Roof  Flashing section in these instructions.

If the overhang is not deep enough to allow the chimney to be fully

installed within the overhang, it will be necessary to cut away a portion

of the overhang.   Ensure that a 2" minimum air space clearance all

around the chimney is established.

  

Framing and flashing the sides of

the opening with suitable sheet metal will be required.  Install a Wall

Band fastened securely to the wall structure directly beneath the

overhang.  The installation of a Universal Roof Brace Kit may be

required if the chimney  exceeds 5 feet or more above the roof.

WALL SUPPORT (WS) - Adjustable up to 6"
from a vertical wall (sold separately)

As previously mentioned, the ideal location for your chimney system

is within the building envelope.  A Wall Support installation is required

when the above mentioned location is not possible.

To complete a proper Wall Support installation, the following parts will

or may be required:

- Wall Support (WS): Intended for a through-the-wall installation where

the chimney has a horizontal connection.  The WS is adjustable  from

2" to 6" from the vertical wall.   NOTE:  The WS is NOT supplied in the

Wall Support Kit.

- Stove Pipe Adaptor (ASE): Transition from chimney to flue pipe.

- Insulated Tee with Insulated Tee Cap: Allowing a horizontal connec-

tion to the chimney.

- Roof  Flashing Assembly: Required when the chimney penetrates a

roof or a roof overhang.

- Rafter Radiation Shield (RRS): Required when the chimney is enclosed

immediately below the roof.

- Wall Band (WB); Universal Wall Band (UWB):Required to provide

lateral support to chimney.

- Suitable Lengths of Chimney: The   chimney diameter should be sized

to suit the appliance.

- Chimney Length: Appropriate length for connection to Tee branch.

- Wall Thimble (WT): Required to pass though a combustible wall.

- Rain Cap: Standard or Deluxe model

The maximum chimney height  above a Wall Support is indicated in Table

4 and illustrated in Figure19, all of which must be above the support.

The Wall Support will allow for an adjustment of  2" to 6" from a vertical

wall.  Threaded studs are factory installed on both side brackets and

the support plate for fast and easy assembly (see

Figure 122).

Ensure the Wall Support Brackets are bolted securely to the wall .

The following steps will assist you in the installation of the Wall Thimble

and of the Wall Support.  Figure 19 shows  a typical Wall Support

installation through a combustible wall.

1. Determine the centre line of  the horizontal connection (Chimney
Length through the wall) and frame an opening to the dimensions

specified for the Wall Thimble in a combustible wall.  See Section A in
Table 3 and Figure 21 (A).

- Use a stud finder to roughly locate the walls studs.  Mark the

Summary of Contents for SUPERPRO SPR

Page 1: ...MBUSTIBLE MATERIALS IT IS OF THE UTMOST IMPORTANCE THAT THIS CHIMNEY SYSTEM BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING YOUR INSTALLATION FAIL...

Page 2: ...RESTOP RADIATION SHIELD INSTALLATION ELBOW INSTALLATION WALL SUPPORT INSTALLATION AWS INTERMEDIATE WALL SUPPORT AIWS WALL SUPPORT INSTALLATION WS WALL BANDS CATHEDRAL CEILING SUPPORT INSTALLATION RAFT...

Page 3: ...3 SELKIRKCANADACORPORATION SELKIRKCANADACORPORATION 09 29 20 09 29 20 CERTIFICATIONLABELS...

Page 4: ...udsistypicallyusedinthissituation Thespace betweentheouterwallofthechimneyandtheenclosuremustbealeast aminimumof2inches MAINTAIN A 2 MINIMUM AIR SPACE CLEARANCE BETWEEN INSULATED CHIMNEY SECTIONS AND...

Page 5: ...ich can affect the operation and or performance of your appliance and or chimney system Plan your installation carefully If possible position the stove so that the flue outlet is between joists rafter...

Page 6: ...nto the Decorator Ceiling Support and slide the assemblyintotheframedopeningfrombelow Ensurethatthefinishing ringisflushwiththeundersideofthefinishedceilingandtheassembly is level and plumb Secure the...

Page 7: ...ler Up and apply pressure to compress the adjoining segments together until the overlapped edge of the Adjustable Length extends down to the reference line marked on the standard length Secure by inst...

Page 8: ...ore securing into place When an Attic Insulation Shield is required above the Decorator CeilingSupportintoanatticasshowninFigure4 ensurethatthebase of the shield is flush with the top of the joist fra...

Page 9: ...a ChimneyLengths mustpassverticallythroughframedjoistareas Two Story Basement Installation Attic Insulation Shield AIS Firestop Radiation Shield FRS Install an Elbow Support on the first Length just a...

Page 10: ...ot cleanout section and or the Insulated Tee Plug which is installed below the support Figure 15 Installtheinteriorinnerhalf withroundplateandtabs ofthewallthimble into the inside wall opening ensurin...

Page 11: ...hole Keep in mind the 2 clearance to the chimney outer surface Install an Attic Insulation Shield if space permits on the under side of the overhang If it is not possible the overhang can be enclosed...

Page 12: ...oping adjustment from 4 1 2 to 8 3 4 2 For a non combustible wall concrete block or poured foundation cut a hole 3 16 greater in diameter than the outside diameter of the chimney as per Table 3 Break...

Page 13: ...into the Tee branchbytwistingclockwise ALockingBandmustthenbeinstalled tosecuretheconnection Makesurethenutandboltarefacingdown to prevent any water from collecting in the Locking Band The Tee branch...

Page 14: ...ew into the nutsert located on the front of the Support Plate see Figures 24 25 and 26 FIGURE 26 Securing of Insulated Tee Cap 14 Use a non hardening high temperature sealant 500 F to seal around the...

Page 15: ...nstalltheInsulatedTeeCapasper step 15 20 It is required to have a Universal Wall Band UWB installed every 8 feet For systems shorter than 8 at least one Universal Wall Band UWB must be installed 21 Pl...

Page 16: ...and by screwing four stainless steelsheetmetalscrewsthroughthedrawbandandintotheoutercasing CeilingTrimAngles CeilingTrimAngles Suitablelengthsofchimney Thechimneydiametershouldbesized to suit the app...

Page 17: ...when exposed to windy conditions NOTE The male coupler of each chimney length must point up RAFTER RADIATION SHIELD RRS ARafterRadiationShield RRS mustbeinstalledwherethechimney is enclosed immediatel...

Page 18: ...the seam of the cone where it meets the plate Apply a bead of silicone caulking along the back seam of the cone Assemble Chimney Sections through the roof opening and Flashing Ensurethatallsectionsar...

Page 19: ...legs by sliding the supplied hose clamp over larger diameter leg and then inserting smaller diameter leg into larger diameter leg Temporarily hold legs together by tightening the hose clampoverthecut...

Page 20: ...o telescoping legs should form an angle of about 60 to give support to the chimney in all directions The angle of the telescoping legs should be approximately 45 from vertical when fastened to the roo...

Page 21: ...the heating season Where coal is burned the system must be thoroughly cleaned within 48 hours of shutting down the system for the season and all soot be removed from the chimney system This should be...

Page 22: ...HIMNEY INSTALLATION It may be necessary to offset the chimney in order to clear a joist or an obstacle The three 3 charts below will assist you in selecting the proper combination of elbow angle and c...

Page 23: ...bands at all joints for added safety and stability This will eliminate the risk of sections becoming undone below the roof line when the Rain Cap is removed when inspections and cleaning of the system...

Page 24: ...Length 18 ChimneyLength 12 ChimneyLength 6 Chimney Length 12 Adjustable Length Tee with Plug Insulated Tee Cap 15o ElbowKit 30o ElbowKit 45 ElbowKit CeilingSupport WallSupport Kit Intermediate Wall Su...

Page 25: ..._________________________________________________ DEALER INFO DEALER NAME _______________________________________________________ Address _____________________________________________________________...

Page 26: ...SI QUE LA GARANTIE DU FABRICANT CONSERVEZ CES DIRECTIVES DANS UN ENDROIT S CURITAIRE AFIN DE POUVOIR VOUS REPORTER AU BESOIN UNE DES CAUSES PRINCIPALES D INCENDIES DE CHEMIN ES EST LE FAIT DE NE PAS M...

Page 27: ...TALLATION DU COUPE FEU DE SOLIVE INSTALLATION DU COUDE INSTALLATION DU SUPPORT MURAL AWS INSTALLATION SUPPORT MURAL INTERM DIAIRE AIWS INSTALLATION DU SUPPORT MURAL WS BRIDES MURALE INSTALLATION DU SU...

Page 28: ...3 SELKIRKCANADACORPORATION SELKIRKCANADACORPORATION 09 29 20 09 29 20 TIQUETTESDECERTIFICATION...

Page 29: ...u elle soit encloisonn e sous la ligne du toit pour la prot ger contre les temp ratures froides ext rieures ceci pourrait r duire la condensation la formation de cr osote et am liorer le tirage Assure...

Page 30: ...es en vous assurant que le d gagement sp cifi de 2 po 50mm aux combustibles soit maintenu Toutes les ouvertures devraient tre de forme carr e tre d aplomb et en alignement parfait avec chacune des aut...

Page 31: ...sch mas 4 10 d montrent les deux types d installation les plus courantes pour un support de plafond d coratif Encadrer compl tement l ouverture carr e les 4 c t s selon les dimensions sp cifier au ta...

Page 32: ...z l isolation du bout femelle de la longueur r glable jusqu ce que l isolation soit de niveau avec la ligne marqu e sur l ext rieur de la longueur sch ma 7 6 Tandis d tre toujours plac avec le bout m...

Page 33: ...air libre entre le coupe feu solive FRS et la structure des solives TABLEAU D ENCADREMENT POUR LE PARE FEU POUR LE GRENIER DIAM TRE DE CHEMIN E OUVERTURE ENCADR E Tableau 2 Enclos Espace habit Solin...

Page 34: ...alement par les zones de solives structur es Installation au sous sol pour deux tages cran thermique pour grenier AIS Coupe feu de solive FRS Chapeaudechemin e Placez le second coude coude de retour p...

Page 35: ...longueurdechemin e install e pr c demmentsurlemanchondut danslabaguemuraleenvousassurantque l accouplement m le sur le t est vers le haut Ins rez et visez l anneau d ancrage dans le bout femelle du t...

Page 36: ...et installez un coupe feu de solive L ouverture devra tre encadr et un coupe feu radiant install install auniveaudutoit Silegrenierestouvertausoffite fermezl acc savec des mat riaux de construction ap...

Page 37: ...ouverture 3 16 po plus grande que le diam tre ext rieur de la chemin e selon le tableau 3 Cr er une petite ouverture pour confirmer que le trou sera centr entre les goujons et q aucuns fils lectriques...

Page 38: ...l espace habit Serrez fermement dans le t en tournant dans le sens horaire Un collier de fixation doit tre install ce raccordement Assurez vous que l crou et le boulon font face vers le bas afin d em...

Page 39: ...ort S curisez en place avec la vis de fixation dans le nutsert situ l avant de la plaque de soutien voir les sch mas 24 25 et 26 SCH MA 26 Fixation du bouchon de t isol 14 Employez un calfeutrant la s...

Page 40: ...se tiennent ensemble Installez un collier de fixation pour prot ger en surplus les deux sections de chemin e Sch ma 30 Sch ma 31 Sch ma 32 Bande universelle Attache d espacement Trous pour boulon de...

Page 41: ...de chemin e ad quates Le diam tre de la chemin e devrait avoir une dimension qui convient l appareil Chapeau de chemin e Mod le r gulier ou deluxe N B Pour r duire l infiltraion d air froid dans le l...

Page 42: ...u radiant RRS doit tre install o la chemin e est enferm e imm diatement sous la ligne de toit tel que d montr au sch ma 39 Un exemple de ceci est quand l espace de grenier d une maison est employ en t...

Page 43: ...chaque c t s en utilisant 12 clous avec rondelles en n opr ne ou couvrez les t tes de clous avec un calfeutrage imperm able l eau non durcissant appropri Scellez les bardeaux la plaque de la m me mani...

Page 44: ...s syst me plus haut un secondaire peut treexig e F Assemblez les jambes t lescopiques en glissant la pince de serrage sur la jambe diam tre sup rieure et ins r e la jambe diam tre inf rieure dans cell...

Page 45: ...t lescopiques devraient former approximativement un anglede60 pourdonnersupport lachemin edanstouteslesdirections Une fois fix au toit l angle des jambes t lescopiques ne devrait pas d passer 45 de l...

Page 46: ...ann e Les entr es d air devraient tre ferm es et scell es au besoin pour emp cher l coulement constant d air dans le syst me AVERTISSEMENT NE PAS UTILISER DE MAT RIAUX COMBUSTIBLES CORROSIFS POUR L EN...

Page 47: ...eurs n cessaires pour obtenir le degr d angle n cessaire dans une hauteur disponible 1 S lectionnez la colonne contenant le diam tre de votre syst me de chemin e 2 D terminez la distance requise pour...

Page 48: ...fortement recommand d utiliser des colliers de fixation sur toutes les longueurs de chemin e pour une s ret et stabilit suppl mentaire lorsque expos s de forts vent au dessus du toit Ceci liminera au...

Page 49: ...o Longueur ajustable 12po T et bouchon Bouchon de t isol Ensemble de coude 15o Ensemble de coude 30o Ensemble de coude 45 Support de plafond Supportmural Supportinterm diaire Supportmural Support cath...

Page 50: ...ION _________________________________________________ INFORMATION DU D TAILLANT NOM DU D TAILLANT _________________________________________________ Adresse ____________________________________________...

Reviews: