background image

10

2

2.5

3

3.5

4

4.5

5

5.5

6

74

73

71

69

66

62

58

52

45

63

62

60

59

56

53

50

45

39

56

55

53

51

49

46

43

38

34

49

48

47

46

44

42

39

35

30

Insulated Wall Thimble

Telescoping adjustment

from 6” to 11”

Insulation

Blanket

Interior Inner

Half of

Insulated Wall

Thimble

Exterior Outer

Half of

Insulated Wall

Thimble

Figure 19

FIG. 20 - SECURING OF INSULATED TEE CAP

Support
Plate

Insulated Tee Cap

Screw to

Secure Tee Cap

Bracket

Tee Cap
Bracket

WARNING:

 The Insulated Tee Cap must be installed

and secured in place.  Failure to install retaining clips

could cause fire, injury or death.

Nutsert

Insulated
Chimney
Section

9.  Place the insulated Tee on the support plate ensuring that the
male coupler of the Tee is facing up and the flange on the top of the
plate slides into the female coupler.  Insert and secure the Tee Cap
with the attached retainer clips (see Figure 20).  In earthquake zones,
secure the Tee to the flange on the support plate by installing 2 stain-
less steel sheet metal screws as per figure 20.

10.  For extension of the Tee, slide an appropriate insulated Chimney
Length through the Wall Thimble and attach it to the horizontal branch of
the Insulated Tee with the supplied locking band.  Make sure the nut and
bolt are facing down to prevent any water from collecting in the locking
band.  The insulated length must  protrude at least 76mm (3”) through
the wall into the room as per Figure 14a.

Stud and Nut

located to front

of Support

Bracket

Support
Brackets

Threaded Stud
and Nut
located at
rear of
Support 

Plate

Pre-
Punched
Holes of
Support
Bracket

Slot for Tee
Cap Bracket

Flange Up

FIG. 18 - FRONT VIEW OF WALL SUPPORT ASSEMBLY

Support
Plate

6.  Ensure that the Wall Support is level, and secure to the wall  through
the pre-punched holes located on the sides of each of the wall support
brackets using (8) #14 x 1-1/2” hex head lag screws or #10 x 1-1/2” wood
screws.  You can drill 5/32” pilot holes for the lag screws.

7.  Once in its final position and all clearances have been met, tighten
each of the nuts on the threaded studs.
8.  Attach the two (2) retainer clips to the bottom of the support plate
and fasten with the supplied nuts and bolts using the two (2) holes on
top of the support plate (see Figure 20).

11.  Use a non-hardening high-temperature sealant (500

o

 F) to seal

around the horizontal length where it enters the wall thimble or the
concrete wall.

12.  Chimney  lengths above the Insulated Tee are simply stacked on
and locked with a 1/8 clockwise turn.  Locking bands must be used
on all joints.

13.  For lateral stability of the chimney above the support, a Wall Band
must be used every 8 feet, and at least one Wall Band must be installed.
Interior chimneys must use the Firestop Joist Shield (JS) in place of Wall
Bands if extending through floor / ceiling penetrations.

Distance from

Wall to

Chimney

5” ID

Chimney

6” ID

Chimney

7” ID

Chimney

8” ID

Chimney

H(feet)

Max. Height

H (feet)

Max. Height

H (feet)

Max. Height

H (feet)

Max. Height

D (inches)

Wall/Chimney

Table 5

 - 

Wall Support Chimney Height Chart

Support Side

Brackets

Support Plate
Threaded Stud

Support Bracket
Threaded Stud

Nut

Support
Plate

Nuts

Nut

Support Bracket
Threaded Stud

Support
Plate
Threaded
Stud

FIG. 17 - UNDERSIDE VIEW OF

THREADED STUDS AND NUTS

Summary of Contents for ULTRA-TEMP UT

Page 1: ...future reference INSTALLATION INSTRUCTIONS MAINTENANCE GUIDE CANADA ONLY Tested to Standard CAN ULC S604 ULC ORD C959 PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING YOUR INSTALLATION FAILURE TO INSTALL THIS SYSTEM IN ACCORDANCE WITH THESE INSTRUCTIONS WILL VOID THE CONDITIONS OF CERTIFICATION AND THE MANUFACTURER S WARRANTY A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARAN...

Page 2: ...NG FRAMINGDETAILS CEILINGSUPPORT ADJUSTABLELENGTH ATTICINSULATIONSHIELD FIRESTOPJOISTSHIELD ELBOWINSTALLATION ADJUSTABLEWALLSUPPORT WALLBAND CATHEDRALCEILINGSUPPORT ROOFSUPPORT ROOFFLASHING UNIVERSALROOFBRACEKIT ROUND TOP AND SPARK ARRESTER STOVEPIPEADAPTER ANCHORPLATE CHIMNEYOPERATIONANDMAINTENANCE OFFSETCHART CHIMNEYCHARTABOVEROOF REPLACEMENTPARTSLIST PRODUCTANDINSTALLATIONINFORMATION TABLEOFCON...

Page 3: ...3 CERTIFICATIONLABELS ...

Page 4: ...they pass The minimum airspace clearance between the outer wall of the chimney and the enclosure shall be at least 2 inches Be sure that electrically powered tools are properly grounded If you are knowledgeable in carpentry and mechanically inclined you can take on the task of installing your new venting system It is impor tant that all pertaining installation instructions and local codes are foll...

Page 5: ...ystem Attic Insulation Shield Where a chimney enters an open attic space Firestop Joist Shield Installed where the chimney passes from one living space to another living space or as specified in the listed factory built fireplace installation instructions Figure3 Typical Roof Joist Framing Figure2 Typical Joist Framing FRAMING DIMENSIONS FOR MODEL UT TO MAINTAIN 2 INCH AIR SPACE CLEARANCE Chimney ...

Page 6: ...at the Adjustable Length be attached and secured to the lower adjoining segment before it is installed in the system 8 Seal the overlap seam and screws with silicone sealant See Fig 8b 7 Re orient the assembly to the upright position Male Coupler Up and apply pressure to compress the adjoining segments together until the overlapped edge of the Adjustable Length extends down to the reference line m...

Page 7: ...pening all four sides controls vertical and horizontal spread of any fire external to the chimney ATTICINSULATIONSHIELD The function of the Attic Insulation Shield or a complete enclosure is to keep insulation from coming into contact with the chimney The height of the Attic Insulation Shield is to meet the insulation level requirement of the National Building Code Where height restrictions will n...

Page 8: ...bing straps not supplied must be installed at 1 2m 4 intervals in conjunction with an offset support Maximum offset length is 4 8m 16 See the Offset Chart for assistance in selecting your offset NOTE Large diameters 10 to 14 may combine elbow kits for a greater angle up to 45 15 Elbow Kit 30 Elbow Kit 45 Elbow Kit MODEL UT Framed Enclosure 2 50mm clearance from chimney to combustible wall Elbow Su...

Page 9: ...talled It is desirable to fully enclose an exterior chimney with minimum of 2 air space clearance to reduce creosote buildup and to promote draft The framing dimensions for the Wall Support are ilustrated in Fig 15 and Table 4 The following steps will assist you in the installation of the Adjustable Wall Support Figure 16 shows a typical Wall Support installation through a combustible wall Through...

Page 10: ...ar of Support Plate Pre Punched Holes of Support Bracket Slot for Tee Cap Bracket Flange Up FIG 18 FRONTVIEW OFWALLSUPPORTASSEMBLY Support Plate 6 Ensure that the Wall Support is level and secure to the wall through the pre punched holes located on the sides of each of the wall support brackets using 8 14 x 1 1 2 hex head lag screws or 10 x 1 1 2 wood screws You can drill 5 32 pilot holes for the ...

Page 11: ...tening the support band with the bolt and nut Secure the band to the chimney outer casing by screwing four stainless steel sheet metal screws through the support band and into the outer casing Lower the chimney length down through the opening in the bottom of the support box so that the Support Band makes contact with the bottom of the Support Box see Figure 24 Cathedral Ceiling Support w 4 painte...

Page 12: ...dditional chimney sections and lock together by turning clock wise until the two sections lock together tightly Locking bands must be used at all joints Continue in this manner until the required height above the roof is achieved Chimney sections installed below the Cathedral Support are locked together from below by turning counter clockwise until tightly locked together with each joint being sec...

Page 13: ...e 28 Apply a non hardening high temperature silicone caulking just above the top of the flashing cone where it meets the chimney casing Slide the Storm Collar through the applied caulking and place into its final position to ensure a waterproof joint Apply additional caulking above the Storm Collar as required The HDURBK will provide lateral support to the chimney above the roof line The HDURBK is...

Page 14: ... bolts and attach the top portion of each of the telescoping legs to the 2 elevator bolts on the Support Band with washers and nut see Figure 34 Leg can be bent at an angle using the claw of a hammer H Attach the other end of each telescoping leg assembly to an Angle Bracket using one 1 1 4 20 X 1 bolt and nut see Figure 35 Preparation of Telescoping Legs F Assemble the telescoping tubes by insert...

Page 15: ... pipe 2 Press down evenly on lower skirt until it contacts upper end of pipe 3 Tighten screw on collar to expand lower end and clamp to inside of pipe Keep tightening screw until collar is expanded and fully tight SPARK ARRESTER Part No SA For 6 to 8 diameters a pre formed Spark Arrester is available See separate instructions packaged with the Spark Arrester Spark Arrester To Install 1 Place the p...

Page 16: ...ect in chimney flue and on termination parts causing reduced flow of gases through the chimney Check top weekly for excessive accumulation of these normal combustion products and clean as necessary If the spark arrester becomes clogged with creosote it should be cleaned or replaced 4 Always secure all single wall flue pipe joints with a minimum of 3 screws 5 Obtain proper attachment parts for the ...

Page 17: ...ou in selecting the proper combination of elbow angle and chimney length s that will provide the necessary degree of offset within an available height 1 Select the column with the proper chimney diameter of your system 2 Determine the distance of the offset required by dropping a plumb line for an accurate measure ment The offset is measured at the chimney cen tre line as per the A Offset measurem...

Page 18: ... and other parts of the house roof could interfere with airflow over and around the top of the chimney and affect its performance If you think a nearby obstacle could affect draft you might want to install one or more additional lengths CHART 2 CHIMNEY HEIGHT ABOVE THE ROOF DISTANCE FROM PEAK 10 Ft 9 Ft 8 Ft 7 Ft 6 Ft 5 Ft 4 Ft 3 Ft 2 Ft 1 Ft CHIMNEY HEIGHT ABOVE ROOF INCHES PITCH OF ROOF Defaulte...

Page 19: ..._______________________________________________ DEALER INFO DEALER NAME _______________________________________________________ Address _____________________________________________________________ City ________________________________________________________________ Province _____________________________________________________________ TECHNICIAN INFO TECHNICIAN NAME _____________________________...

Reviews: