background image

7

A

B

C

D

E

“A” DIM.

“B” DIM.

“C” DIM.

“D” DIM.

“E” DIM.

7 -1/4”

11”

11-13/16”

13”

20”

8 -1/4”

12”

11-13/16”

14”

20”

9 -1/4”

13”

11-13/16”

15”

20”

10 -1/4”

14”

11-13/16”

16”

20”

12 -1/4”

16”

11-13/16”

18”

20”

14 -1/4”

18”

11-13/16”

20”

20”

5”

11 x 11

6”

12 x 12

7”

13 x 13

8”

14 x 14

10”

16 x 16

12”

18 x 18

16 -1/4”

20”

11-13/16”

22”

20”

14”

20 x 20

DIM “ A”

(Non Standard Length)

Remove Insulation
Down to This Line

DIM “A”

+ 2.25”

Fig. 6

Fig. 7

Fig. 8a

Install Sheet Metal
Screws Through
Pilot Holes and
Into Outer Wall of
Standard Length

DIM “A” +

2.25”

Insert Standard Length While Ori-
ented as Shown to Avoid Insula-
tion Spillage

Adjustable

Length

Standard

Length

Adjustable

Length

Fig. 8b

Seal Overlap Seam
and Screws With
Silicone Sealant

Standard

Length

Adjustable Length Attached
to Standard Length

Adjustable

Length

Reference

Line

Overlap

Standard

Length

Mark an Overlap Refer-
ence Line on the Standard
Length. (The Overlap Dis-
tance is Dim “B” Plus 1”)

Standard

Length

Ensure Adjust-
able Length Edge
is Even With  Ref-
erence Line

Standard

Length

DIM “B”

Male End

- It stabilizes the chimney in the framed opening and defines and
maintains the required AIR SPACE clearance to combustibles.
- It prevents heat losses from the dwelling by blocking vertical air
circulation in the space around the chimney.
- It helps provide stability for chimney extending above the roof.

FIRESTOPPING:

Firestopping is required at every joist level.  Wherever a chimney
passes through a ceiling or floor, through a wall, or into an enclosure,
it must be firestopped.   No firestopping is required in conjunction
with a Ceiling Support installed as shown in Figure 5,  the Ceiling
Support provides the firestopping.   Firestopping performs the follow-
ing essential functions for both the dwelling and the chimney.

- Together with a fully framed opening (all four sides), controls vertical
and horizontal spread of any fire external to the chimney.

ATTIC INSULATION SHIELD

The function of the Attic Insulation Shield (or a complete enclosure) is
to keep insulation from coming into contact with the chimney.   The
height of the Attic Insulation Shield is to meet the insulation level
requirement of the National Building Code.  Where height restrictions
will not permit the use of the Attic Insulation Shield, it is permissible to
construct an enclosure with the required air space clearance to the
outer pipe all the way to the underside of the roof deck.  In this appli-
cation you would install a Firestop/Joist Shield on the ceiling side.

UT

Chimney

Pipe

Integrated

Storm Collar

Attic Insulation
Shield (AIS)

Telescoping

Joist Shield

FIGURE 9

- At the level where the chimney penetrates the air/vapour barrier, spe-
cial attention is required.  Seal the vapour barrier to the Support Assem-
bly or Attic Insulation Shield or Wall Thimble or Firestop using an appro-
priate caulking compound as per the requirement of local authorities.

FRAMING DIMENSION  CHART

FOR ATTIC INSULATION SHIELD

DIA. OF

CHIMNEY

FRAMED

OPENING

Table 2

For proper installation, the attic opening should be fully framed at 2
inches clearance to the chimney pipe with framing material of the same
dimension as the ceiling joists as per Table 2 and Figure 10.  The tabs
on the base plate of the AIS are inserted in the framed opening around
the chimney.

The Attic Insulation Shield allows for a depth of insulation of 10 inches
plus the depth of the ceiling joists.  If insulation is blown in and ad-
heres to the chimney pipe, it should be brushed off to eliminate any
possible contact of this material with the chimney surface.

Nail the AIS base to the framing dimensions with at least 2 nails per
side using 2d (1”) spiral nails or 1” x #8 wood screws.  Extend the
telescoping shield down through the framing.  See Figures 9 and 10.

FIGURE 10

Summary of Contents for ULTRA-TEMP UT

Page 1: ...future reference INSTALLATION INSTRUCTIONS MAINTENANCE GUIDE CANADA ONLY Tested to Standard CAN ULC S604 ULC ORD C959 PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING YOUR INSTALLATION FAILURE TO INSTALL THIS SYSTEM IN ACCORDANCE WITH THESE INSTRUCTIONS WILL VOID THE CONDITIONS OF CERTIFICATION AND THE MANUFACTURER S WARRANTY A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARAN...

Page 2: ...NG FRAMINGDETAILS CEILINGSUPPORT ADJUSTABLELENGTH ATTICINSULATIONSHIELD FIRESTOPJOISTSHIELD ELBOWINSTALLATION ADJUSTABLEWALLSUPPORT WALLBAND CATHEDRALCEILINGSUPPORT ROOFSUPPORT ROOFFLASHING UNIVERSALROOFBRACEKIT ROUND TOP AND SPARK ARRESTER STOVEPIPEADAPTER ANCHORPLATE CHIMNEYOPERATIONANDMAINTENANCE OFFSETCHART CHIMNEYCHARTABOVEROOF REPLACEMENTPARTSLIST PRODUCTANDINSTALLATIONINFORMATION TABLEOFCON...

Page 3: ...3 CERTIFICATIONLABELS ...

Page 4: ...they pass The minimum airspace clearance between the outer wall of the chimney and the enclosure shall be at least 2 inches Be sure that electrically powered tools are properly grounded If you are knowledgeable in carpentry and mechanically inclined you can take on the task of installing your new venting system It is impor tant that all pertaining installation instructions and local codes are foll...

Page 5: ...ystem Attic Insulation Shield Where a chimney enters an open attic space Firestop Joist Shield Installed where the chimney passes from one living space to another living space or as specified in the listed factory built fireplace installation instructions Figure3 Typical Roof Joist Framing Figure2 Typical Joist Framing FRAMING DIMENSIONS FOR MODEL UT TO MAINTAIN 2 INCH AIR SPACE CLEARANCE Chimney ...

Page 6: ...at the Adjustable Length be attached and secured to the lower adjoining segment before it is installed in the system 8 Seal the overlap seam and screws with silicone sealant See Fig 8b 7 Re orient the assembly to the upright position Male Coupler Up and apply pressure to compress the adjoining segments together until the overlapped edge of the Adjustable Length extends down to the reference line m...

Page 7: ...pening all four sides controls vertical and horizontal spread of any fire external to the chimney ATTICINSULATIONSHIELD The function of the Attic Insulation Shield or a complete enclosure is to keep insulation from coming into contact with the chimney The height of the Attic Insulation Shield is to meet the insulation level requirement of the National Building Code Where height restrictions will n...

Page 8: ...bing straps not supplied must be installed at 1 2m 4 intervals in conjunction with an offset support Maximum offset length is 4 8m 16 See the Offset Chart for assistance in selecting your offset NOTE Large diameters 10 to 14 may combine elbow kits for a greater angle up to 45 15 Elbow Kit 30 Elbow Kit 45 Elbow Kit MODEL UT Framed Enclosure 2 50mm clearance from chimney to combustible wall Elbow Su...

Page 9: ...talled It is desirable to fully enclose an exterior chimney with minimum of 2 air space clearance to reduce creosote buildup and to promote draft The framing dimensions for the Wall Support are ilustrated in Fig 15 and Table 4 The following steps will assist you in the installation of the Adjustable Wall Support Figure 16 shows a typical Wall Support installation through a combustible wall Through...

Page 10: ...ar of Support Plate Pre Punched Holes of Support Bracket Slot for Tee Cap Bracket Flange Up FIG 18 FRONTVIEW OFWALLSUPPORTASSEMBLY Support Plate 6 Ensure that the Wall Support is level and secure to the wall through the pre punched holes located on the sides of each of the wall support brackets using 8 14 x 1 1 2 hex head lag screws or 10 x 1 1 2 wood screws You can drill 5 32 pilot holes for the ...

Page 11: ...tening the support band with the bolt and nut Secure the band to the chimney outer casing by screwing four stainless steel sheet metal screws through the support band and into the outer casing Lower the chimney length down through the opening in the bottom of the support box so that the Support Band makes contact with the bottom of the Support Box see Figure 24 Cathedral Ceiling Support w 4 painte...

Page 12: ...dditional chimney sections and lock together by turning clock wise until the two sections lock together tightly Locking bands must be used at all joints Continue in this manner until the required height above the roof is achieved Chimney sections installed below the Cathedral Support are locked together from below by turning counter clockwise until tightly locked together with each joint being sec...

Page 13: ...e 28 Apply a non hardening high temperature silicone caulking just above the top of the flashing cone where it meets the chimney casing Slide the Storm Collar through the applied caulking and place into its final position to ensure a waterproof joint Apply additional caulking above the Storm Collar as required The HDURBK will provide lateral support to the chimney above the roof line The HDURBK is...

Page 14: ... bolts and attach the top portion of each of the telescoping legs to the 2 elevator bolts on the Support Band with washers and nut see Figure 34 Leg can be bent at an angle using the claw of a hammer H Attach the other end of each telescoping leg assembly to an Angle Bracket using one 1 1 4 20 X 1 bolt and nut see Figure 35 Preparation of Telescoping Legs F Assemble the telescoping tubes by insert...

Page 15: ... pipe 2 Press down evenly on lower skirt until it contacts upper end of pipe 3 Tighten screw on collar to expand lower end and clamp to inside of pipe Keep tightening screw until collar is expanded and fully tight SPARK ARRESTER Part No SA For 6 to 8 diameters a pre formed Spark Arrester is available See separate instructions packaged with the Spark Arrester Spark Arrester To Install 1 Place the p...

Page 16: ...ect in chimney flue and on termination parts causing reduced flow of gases through the chimney Check top weekly for excessive accumulation of these normal combustion products and clean as necessary If the spark arrester becomes clogged with creosote it should be cleaned or replaced 4 Always secure all single wall flue pipe joints with a minimum of 3 screws 5 Obtain proper attachment parts for the ...

Page 17: ...ou in selecting the proper combination of elbow angle and chimney length s that will provide the necessary degree of offset within an available height 1 Select the column with the proper chimney diameter of your system 2 Determine the distance of the offset required by dropping a plumb line for an accurate measure ment The offset is measured at the chimney cen tre line as per the A Offset measurem...

Page 18: ... and other parts of the house roof could interfere with airflow over and around the top of the chimney and affect its performance If you think a nearby obstacle could affect draft you might want to install one or more additional lengths CHART 2 CHIMNEY HEIGHT ABOVE THE ROOF DISTANCE FROM PEAK 10 Ft 9 Ft 8 Ft 7 Ft 6 Ft 5 Ft 4 Ft 3 Ft 2 Ft 1 Ft CHIMNEY HEIGHT ABOVE ROOF INCHES PITCH OF ROOF Defaulte...

Page 19: ..._______________________________________________ DEALER INFO DEALER NAME _______________________________________________________ Address _____________________________________________________________ City ________________________________________________________________ Province _____________________________________________________________ TECHNICIAN INFO TECHNICIAN NAME _____________________________...

Reviews: