background image

Page 6

X          X           X           X

X          X           X           X

            X           X           X

         

127mm       152mm        178mm        203mm

183

(7-3/16”)

210

(8-3/16”)

233

(9-3/16”)

259

(10-3/16”)

280 x 280

11” x 11”

305 x 305

12” x 12”

330 x 330

13” x 13”

356 x 356

14” x 14”

Table 3

Table 4

Chimney Size                                               5”                   6”                  7”                   8”

Minimum Framed Opening for
Combustible Wall

Minimum Round Hole
Diam. For Non-Combustible Wall

The female end of the elbows are not 

lanced

 in order to ensure

proper alignment of the chimney system can be maintained.

Install and position the insulated elbow on the vertical chimney
length in the required direction.  Fasten the elbow to the chimney
length with the supplied locking band.

Place the required offset chimney length(s) (see Offset Chart for
appropriate length(s)) on the elbow.  Turn it clockwise to lock it in
place and install the supplied locking band.

Install the remaining offset elbow to return the chimney back to
the vertical position.  Again secure in place with the supplied
locking band.  *Locking bands and/or stainless steel sheet  metal
screws can be utilised with a maximum length of 12.70mm (1/2”)
only on all chimney joints forming an offset.

During installation provide supplementary support for the offset
section to avoid undue stress on connected elbows.

Install an Elbow Support on the vertical length just above the
highest elbow.  Securely clamp the support band to the chimney
length just above the locking band at the joint.  Attach the support
straps to the support band assembly and nail them to the framing
using 1-1/2” nails or #8 x 1-1/2” wood screws (2 per straps) as
per Figure 7.

Never install an elbow in a joist area.  Chimney sections must
pass vertically through framed joist areas.

ELBOW INSTALLATION

Elbow Kits (2 elbows, 1 offset support and 4 locking bands).

FIGURE 7

Attic Insulation Shield

Storm Collar

Elbow

Locking Bands

Intermediate/Elbow
Support Straps

Locking Bands

Elbow

Ceiling Support

Roof Flashing

If the offset length is more than 1.2m (4’), an intermediate support
must be employed at 1.2m (4’) intervals.  Maximum offset length
4.8 m (16’), the intermediate support must be used in conjunction
with an offset support.

Round Top

ADJUSTABLE   W ALL SUPPOR T

As previously mentioned, the ideal location for your chimney
system is within the building envelope.  An Adjustable Wall
Support is required when the above mentioned location is not
possible.

The adjustable Wall Support  will allow for an adjustment of 2” to
6” from a vertical wall.  Threaded studs are factory installed on
both side brackets and the support plate for fast and easy
assembly (see Figure 9).

One pair only of (two) 15 or 30 or 45 degree elbows may be used
to provide an offset in order to avoid cutting of joists and to clear
other obstructions.  The vertical run of chimney above an offset
must be supported with an elbow support.  Each elbow support
will support 10m (30’) of chimney.  If the offset length is more than
1.2m (4’), an intermediate support (plumbing straps not supplied)
must be installed at 1.2m (4’) intervals in conjunction with an offset
support.  Maximum offset length is 4.8m (16’).  See Figure 7 and
the Offset Chart for assistance in selecting your offset.

15° Elbow Kit

30° Elbow Kit

45° Elbow Kit

MODEL UT

Framed Enclosure 2”
(50mm) clearance from
chimney to combustible
wall

Elbow Support Band

Roof Joist
(Framed all 4 sides)

Chimney Section

Lower
Bucket

Stove
Pipe
Adapter

Floor, Ceiling Joist
(Framed all 4 sides)

5”         6”         7”         8”

Summary of Contents for ULTRA-TEMP

Page 1: ...MATERIALS MODEL IT IS OF THE UTMOST IMPORTANCE THAT THIS CHIMNEY BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNINGYOUR INSTALLATION FAILURETO INSTAL...

Page 2: ...ZING FRAMINGDETAILS CEILINGSUPPORT ATTICINSULATIONSHIELD FIRESTOPJOISTSHIELD ELBOWINSTALLATION ADJUSTABLEWALLSUPPORT WALLBAND CATHEDRALCEILINGSUPPORT ROOFSUPPORT ROOFFLASHING UNIVERSALROOFBRACEKIT ROU...

Page 3: ...chimney passes Safety gloves Safety goggles Hammer and nails Tin snips Tape measure Scewdrivers and pliers Plumb line and level Square Keyhole say or power jig saw Caulking gun and caulking Be sure th...

Page 4: ...uld conform to Table 1 2 With the Lower Bucket removed place the upper bucket assembly into the framed opening from below 3 Ensure that the support plate is level and flush and drive one nail 1 1 2 co...

Page 5: ...le contact of this material with the chimney surface FIRESTOP JOIST SHIELD A Firestop Joist Shield must be installed where the chimney passes from one living space to another living space It is instal...

Page 6: ...sections must pass vertically through framed joist areas ELBOW INSTALLATION Elbow Kits 2 elbows 1 offset support and 4 locking bands FIGURE7 Attic Insulation Shield Storm Collar Elbow Locking Bands I...

Page 7: ...ified in the Framing Dimensions in Table 1 install the outer half with the unfinished square plate of the Insulated Wall Thimble in the outside wall opening Secure in place using appropriate fasteners...

Page 8: ...t Brackets Threaded Stud and Nut located at rear of Support Plate Pre Punched Holes of Support Bracket Flange Up Holes for Retainer Clips FIG 10 FRONTVIEW OFWALLSUPPORTASSEMBLY Support Plate 6 Ensure...

Page 9: ...the Wall Band bracket to the wall using two 6d or 2 spiral nails For concrete walls use suitable masonry fasteners The nut and bolt supplied will fasten the band around the chimney Figure 16 After fra...

Page 10: ...Brackets to the roof pitch and tighten nuts Attach to the roof with six 6 large wood screws per bracket with the inner most screws going into the rafters or headers See Figure 18 19 9 Additional chim...

Page 11: ...he flashing under the roofing shingles At least half of the flashing top and sides should be UNDER the shingles and the lower end OVER the shingles to provide a watershed Trimming off the shingles may...

Page 12: ...top surface of the length Wrap the band snug to the bottom of the 3 tabs and secure in place with the supplied nut and bolt The connection of a single wall base tee or single wall flue pipe or double...

Page 13: ...artment 4 Do not use salt or water on the fire Salt is corrosive and water will cause a dangerous steam explosion You may be able to control the fire by using ashes sand or baking soda since baking so...

Page 14: ...eter 8 Diameter 5 Diameter 30o OFFSET CHART Chimney Lengths 7 Diameter 6 Diameter 8 Diameter 5 Diameter none 6 12 18 24 12 18 36 12 36 18 36 12 18 36 48 OFFSET CHART CHIMNEY INSTALLATION It may be nec...

Page 15: ...affect its performance If you think a nearby obstacle could affect draft you might want to install one or more additional lengths CHART 2 CHIMNEY HEIGHT ABOVE THE ROOF DISTANCE FROM PEAK 10 Ft 9 Ft 8...

Page 16: ..._______________________________________ Address ______________________________________________________ City _________________________________________________________ Province _________________________...

Reviews: