TECHNICAL SPECIFICATIONS

POWER SUPPLY

Voltage 
Absorption 
Internal battery (buffer)

 

 15 V

, 500 mA Max.

3.5 W Max.

Lithium Ion 3.7 V - 1000 mAh, rechargeable.

DIGITAL INPUTS

Type

Maximum frequency 
Threshold OFF
Threshold ON

4 imput

Reed, contacto, PNP, Pulscap

30 Hz

 3 V

, I < 1mA

 24 V

, I > 3mA

ANALOGUE INPUTS

Type
Accuracy

2 inputs
Voltage 

 30 V

 / Current 0 

 20 mA

0.1% on the full scale

VOLTAGE OUTPUT:

+12 

V

 50 mA (maximum current)

TEMPERATURE SENSOR

NTC thermistor, internal, external ( optional)

USB PORT

1 micro USB for configuration and power supply

DISPLAY

128 x 32 LCD Dots with visible area of 39 mm x 8.6 mm

CONNECTIONS

Spring clamps, 3.5 mm pitch, connector for Micro USB and SMA 
connector for GSM Antenna, MMCX for GPS (optional)

CPU

ARM 100 Mhz 32 bit

INTERNAL MEMORY

FLASH 1 MB (program) + 8 MB (log + data)

Micro SD slot 

Type / Memory

Push-Push per SD card e SD HC card / max 32GB

SIM slot 

Type

Push-Push for mini SIM (15 x 25 mm)

GSM

Quad band (850 / 900 / 1800 / 1900 MHz)

STANDARDS

ETSI EN 301 489-7 - EN301 511 - EN301 489-1 - IEC / EN 60950

ENVIRONMENTAL CONDITIONS

Temperature

Humidity
Storage temperature

Protection rating

Seneca recommends use at 0 to 45 ° C for correct operation.

With the power supply present:

   -   20 .. + 55 °C.  

With use of the battery (when discharged):        -20 .. + 45 ° C.  
Charging is possible in the range:

 

0 .. +45°C. 

30% – 90%, non condensing.
from -20 ° C to +20 ° C <1 year; from -20 ° C to +45 ° C <3 months;
from -20 °C to +60 °C < 1 

P20

 

GPS CARD SPECIFICATIONS (OPTIONAL)    

 

 

RECEIVER

 

22 channels

 

SENSITIVITY

 

-165 dBm

 

FIX TIME

 

32 s usually

 

ACCURACY

 

up to 2.5 m

 

 

 

RELAY EXPANSION CARD SPECIFICATIONS (OPTIONAL)  

 

 

 

DIGITAL 
OUTPUTS

 

2 outputs

 

Relay 3 A max - 250V SPST (with shared terminal)

 

 

 

 

 

 

 

ENGLISH - 3/8

 

Summary of Contents for MyAlarm SEAL

Page 1: ...E ENGLISH 1 8 E E INSTALLATION MANUAL MyAlarm SEAL GSM GPRS datalogger with built in I Os telecontrol functions and advanced programming language This document is the property of SENECA srl Copies and...

Page 2: ...NARY WARNINGS Electrical and electronic waste disposal applicable in the European Union and other countries with recycling programs The symbol on the product or its packaging shows that the product mu...

Page 3: ...ional CPU ARM 100 Mhz 32 bit INTERNAL MEMORY FLASH 1 MB program 8 MB log data Micro SD slot Type Memory Push Push per SD card e SD HC card max 32GB SIM slot Type Push Push for mini SIM 15 x 25 mm GSM...

Page 4: ...the internal battery use the power cord with cigarette lighter socket equipped with a fuse connecting the cables to the and GND terminals a PC via the micro USB port with a standard cable Power suppl...

Page 5: ...s best to place the MyAlarm SEAL in an area not covered by metal structures If this is not possible an optional external antenna with 3m cable code AGPS is available Follow the procedure supplied with...

Page 6: ...ly 6 15 V Digital input 1 Digital input 2 Digital input 3 Digital input 4 12 V output max 50 mA Analog input 1 Analog input 2 Ground 1 2 3 4 5 6 7 8 9 10 11 12 13 Available only with relay board optio...

Page 7: ...ey is illustrated in the initial powering paragraf Press and hold down the left PWR key for several seconds to open the main menu To choose the desired command use the SCR key This button allows you t...

Page 8: ...tion sales seneca it ENGLISH 8 8 ORDER CODE A GPS External GPS antenna with 3 m cable A GSM QUAD N External GSM QUAND N antenna with 5 m cable NTC EXTERNAL TERMISTOR My SEAL O R O W O G B G S REL O ab...

Reviews: