USER MANUAL – RTU-LP-ST
33
ACTION CODE
INFO
1
OUT 1 RESET
2
OUT 2 RESET
4
OUT 1 SET
8
OUT 2 SET
16
OUT 1 TOGGLE
32
OUT 2 TOGGLE
68
OUT 1 START PULSE
132
OUT 2 START PULSE
256
TOTALIZER 1 RESET TO 0
512
TOTALIZER 2 RESET TO 0
1024
TOTALIZER 3 RESET TO 0
2048
TOTALIZER 4 RESET TO 0
65535
RTU RESET
ddmmyyyyhhmm = sending date and sending time
The RTU response is:
AZ OK /
ddmmyyhhmm:RTUCODE
Example of usage:
AZ 4 1005171102
Execute a Digital Output 1 SET
10.6.
AZ – Synchronize DATE/HOUR
The “AZ” SMS message can be used also for sync date/hour using an offset:
AZ ±aaaa±MM±dd±hh±mm±ss ddmmyyhhmm