EasyBuilder Pro Software Settings 

Launch EasyBuilder Pro software, select your 
project file, press F7 shortcut key to open the 
download dialog box:   

Select Ethernet > IP tab > Enter 
your HMI IP > Click Download to download this 
project file to HMI. 

It is recommended to use screensaver and 
backlight saver to avoid image persistence 
caused by displaying the same image on HMI 
for a long time. 

( Please refer to EasyBuilder Pro User Manual 
  for software operation details ) 

Communication Connections 

NOTE: 1. COM2 and COM3 RS-485 2W support MPI 187.5K, please use one at a time. 

2. Only Tx & Rx (no RTS/CTS) may be used for COM1 RS-232 when COM3 RS-232 is also

used. 

Con.B

Con.A 

COM1

/

COM3 [RS232] 9 Pin, Male, D-sub 

  COM2

/

COM3 [RS485] 9 Pin, Female, D-sub 

Jumper Settings 

Please prepare a jumper cap for setting the jumpers.

 

Another way to enter touch screen calibration mode is: Press and hold anywhere on the screen for more 
than 2 seconds when HMI starts.

NOTE: 

Make  sure  that  all  local  and  national  electrical  standards  are  met  when 

installing the unit. Contact your local authorities to determine which codes apply.

 

Power

 

The unit can be powered by DC power only, voltage range: 10.5~28VDC, compatible with most 

controller DC systems. The power conditioning  circuitry  inside the  unit is accomplished  by a 

switching power supply. The peak starting current can be as high as 2A. 

 

Fusing 
Require- 
ments

 

If the display does not come on within 5 seconds of power up, remove power. An internal fuse 

will  prevent  damage  if  the  polarity  of  the  DC  power  is  incorrect.  Check  wiring  for  proper 

connections and try to power up again. 

High Voltage

 

An Internal fuse will prevent damage for overcurrent 

condition however it isn’t guaranteed. DC 

voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with 

ICS Safety Recommendations. 

 

Supply Voltage 
Condition

 

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same 

power  supply.  Note:  The  12  or  24  VDC  output  from  some  controllers  may  not  have  enough 

current to power the unit.

Wire Routing

 

a.

Power wire length should be minimized (Max: 500m shielded, 300m unshielded).

b.

Please use twisted pair cables for power wire and signal wire and conform to the 

impedance matching.

c.  If wiring is to be exposed to lightning or surges, use appropriate surge suppression 

devices.

d.

Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.

e.

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC 

power supply and the frame ground. This provides a path for static and high frequency 

dissipation. Typical values to use are 1M Ohm and 4700pF

 

Hardware 
Considerations

 

The  system  designer  should  be  aware  that  devices  in  Controller  systems  could  fail  and 

thereby  create  an  unsafe  condition.  Furthermore,  electrical  interference  in  an  operator 

interface  can  lead  to  equipment  start-up,  which  could  result  in  property  damage  and/or 

physical injury to the operator. 

If  you  use  any  programmable  control  systems  that  require  an  operator,  be  aware  that  this 

potential safety hazard exists and take appropriate precautions. Although the specific design 

steps  depend  on  your  particular  application,  the  following  precautions  generally  apply  to 

installation  of  solid-state  programmable  control  devices,  and  conform  to  the  guidelines  for 

installation of Controllers recommended in NEMA ICS 3-304 Control Standards.

 

 

Programming 
Considerations

 

To conform  with  ICS Safety  Recommendations, checks should be placed in  the controller to 

ensure  that  all  writable  registers  that  control  critical  parts  of  plant  or  machinery  have  limit 

checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of 

personnel. 

DANGER 

CAUTION 

1-2

3-4

Mode 

Short 

Open 

Touch Screen Calibration Mode & 
Restore Factory Default 

Open 

Short 

Boot Loader Mode 

Open 

Open 

Normal 

Limited Warranty 

This product is limited warranted against defects in design and manufacture.  

The proven defective product will either be repaired or replaced, at 

SENECA

’s 

discretion. This warranty shall not cover any product which is  

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.

PIN# 

COM1 

[RS232] 

COM3 

[RS232] 

RxD 

TxD 

GND 
GND

RTS 

TxD 

CTS 

RxD 

GND 

PIN# 

COM2 

[RS485]2w 

COM2 

[RS485]4W 

COM3 

[RS485] 2W 

Data- 

Rx- 

Data+ 

Rx+ 

Tx- 

Tx+ 

GND

 

Data- 

Data+

 

CAUTION

NN

NOTE: 

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 

CAUTION

NN

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 