USER MANUAL – Z-GPRS2 / Z-LOGGER
81
To receive more files in a directory use the command mget (multiple get).
28.4.
Modbus TCP-IP server
The Modbus TCP-IP server service provides access to Z-GPRS2 / Z-Logger variable Modbus
registers.
In addition to the embedded I/O variables, log variables can be accessed in real-time.
List of Modbus registers:
MSW “Most Significant Word” – Most significant 16 bit word
LSW “Less Significant Word” – Least significant 16 bit word
0x -Hexadecimal value
MODBUS ADDRESS
REGISTER CONTENT
40006
DIGITAL INPUTS
BIT 0 = INPUT 1
BIT 1 = INPUT 2
BIT 2 = INPUT 3
BIT 3 = INPUT 4