MI000692-E
ENGLISH - 4/4
CHANNEL 2 INPUT (Z110D only)
CHANNEL 2 OUPUT (Z110D only)
PASSIVE INPUT
: Connect the module in the current
loop as shown.
The module is powered by the 4 to 20mA current
loop.
Voltage Drop at 20mA: 3.8V plus Load Volt drop
(0.02*load resistance), minimum 7V
(e.g. with load of 250ohm Volt Drop is :
3.8V + (0.02*250) = 8.80V)
ACTIVE OUTPUT
: The module generates a current
in the output loop identical to the
current in the input loop. It is capable of driving into a
maximum load of 500_.
The output loop must NOT be powered.
7 8 9
mA
+
mA
+
4 5 6
Disposal of Electrical & Electronic Equipment (Applicable throughout the European Union and other
European countries with separate collection programs)
This symbol, found on your product or on its packaging, indicates that this product should not be treated as
household waste when you wish to dispose of it. Instead, it should be handed over to an applicable
collection point for the recycling of electrical and electronic equipment. By ensuring this product is
disposed of correctly, you will help prevent potential negative consequences to the environment and
human health, which could otherwise be caused by inappropriate disposal of this product. The recycling of
materials will help to conserve natural resources. For more detailed information about the recycling of this
product, please contact your local city office, waste disposal service or thè retail store where you
purchased this product.
SENECA s.r.l.
Via Austria, 26 - 35127 - PADOVA - ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
e-mail: info@seneca.it - www.seneca.it
This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized. Contents of the
present documentation refers to products and technologies described in it. All technical data contained in the document
may be modified without prior notice Content of this documentation is subject to periodical revision.