Warning:

 

 

Do not use any SonaSwitch

™ 

Ultrasonic Sensor in any application 

to protect human life, health or safety or in any application where 

failure of a SonaSwitch

™ 

Ultrasonic Sensor may result in human 

injury or death.  This sensor must not be used in any environment 

where risk of an explosion is possible. 

 

General:

 

 

This operations and installation manual will provide general guide-

lines and suggestions in using the SonaSwitch

™ 

1650S Laser 

series sonar detection module in many detection applications. If 

further technical information is required, please contact us at in-

fo@edpcompany.com.

 

 

System Wiring:

 

 

1

-

RED

 

Power supply: requires 10

-

30 VDC or 12

-

24 

VAC with 1 ampere minimum current capac-

ity.

 

 

2

-

BLACK

 

Return for AC power supply.

 

 

3

-

WHITE

 

*Output relay 1: normally open (closes dur-

ing detection).

 

 

4

-

YELLOW

 

*Output relay 1: relay common.

 

 

5

-

ORANGE

 

*Output relay 1: normally closed (opens 

during detection).

 

 

6

-

BLUE

 

External Trigger [Clock input: requires TTL 

compatible logic level clock signals (0

-

VDC)].

 

 

 

7

-

BROWN        ECHO Output. (PWM) 0

-

5 volt TTL

 

 

8

-

GREEN         GND (Return for DC power supply and 

clock signals).

 

 

9

-

VIOLET         *Output relay 2: normally open (closes dur-

ing detection).

 

 

10

-

GRAY         *Output relay 2: relay common.

 

 

11

-

PINK           *Output relay 1: normally closed (opens 

during detection).

 

 

12

-

BRN/WHT   Not Used.

 

 

13

-

BLK/WHT    EXT. Trigger Enable (Active Lo).

 

 

14

-

RED/WHT   REC Output (Actual returned echo

s from 

target. TTL level).

 

 

15

-

Light GRN   LASER ENABLE (Connect to supply 

ground ).

 

 

*Relay contacts are dry, rated at 3.0 amperes, 28 VDC, non

-

inductive loads.   Exceeding these limits will cause perma-

nent damage and void warranty.

 

 

 

 

 

General Installation Procedures:

 

 

1.

 

Always mount SonaSwitch

™ 

1650S in a suitable, dry 

location.  The SonaSwitch

™ 

1650S has been designed 

for indoor or protected environments only.  Excessive 

moisture in the circuit board/transducer area will result in 

damage and improper operation of unit and will void all 

manufacturer

s warranties.

 

2.

 

Mount SonaSwitch

™ 

1650S as far off the ground as 

possible (minimum of 24 inches).

 

3.

 

Adjust gain to minimum setting required to insure relia-

ble target detection.  Excessive gain may result in false 

detection.

 

4.

 

Mount the unit in a location where environmental inter-

ference sources are minimized (example: EMI sources, 

air nozzles, excessive air turbulence, etc.).

 

 

Calibration Procedure:

 

See figure 1. 

 

 

1.

 

Apply power to sensor.

 

2.

 

Allow several minutes times to warm

-

up before calibra-

tion.

 

3.

 

Set GAIN pot to 50%.

 

4.

 

To set Range 1, place the target at the desired distance 

in front of the sensor. Push and hold the Range 1 button 

for 3 seconds, when you hear a 

Chirp

” 

release the but-

ton.

 

5.

 

To set Range 2, place the target at the desired distance 

in front of the sensor. Push and hold the Range 2 button 

for 3 seconds, when you hear a 

Chirp

” 

release the but-

ton.

 

6.

 

To calibrate the GAIN, place the target at the maximum 

desired detection distance in front of the sensor. Now 

decrease the GAIN adjust by rotating the potentiometer 

CCW until the target is no longer detected. Next, in-

crease the  GAIN by turning the GAIN adjust CW just 

until the target is detected, give the potentiometer an 

additional 1/16 of a turn CW.

 

 

NOTE: 

ALWAYS SET THE 

GAIN FOR MINIMUM AMOUNT 

NEEDED FOR DETECTION. EXCESSIVE 

GAIN

’ 

MAY RE-

SULT IN FALSE DETECTIONS.

 

 

7.

 

Test the Range settings by slowly moving the target 

towards and away from the sensor. Note that the corre-

sponding LED will be ON when the target is within the 

set Range and the relays will active. Re

-

set Range set-

ting as required.

 

 

Note: Range settings are independent of air temperatures.

 

 

GAIN Adj.

 

(1

-

turn)

 

RANGE 1

 

RANGE 2

 

Figure 1

 

Laser

 

Enable

 

Laser Pointer:

 

 

Use the Laser point as an aide to aiming the sensor at the desired 

target.

 

Note: Laser pointer is accurate to /

-

 3 Inches of  the center point of the sensor.

 

 

 

To activate the Laser pointer push and hold the Laser Enable button 

on the side of the sensor (fig.1) or by tying pin 15 of the DB

-

15 con-

nector on the sensor to ground.  

 

 

 