CamCor CT and PRO Series Hardware Manual
73
Section 8
No.
Item
Description
Procedure Location
Default
2-4-1-1
Assign
Change Analog Output 1 assignment (see
Analog Output Function, page 101
). If assignment is changed,
reconfigure upper limit (No. 2-4-1-2), lower limit (No. 2-4-1-3), low cutoff (No. 2-4-1-4) and damping factor
(No. 2-4-1-5) for optimum settings.
Volume
Flow
2-4-1-2
URV
Change Analog Output 1 upper limit. A 20-mA output will be produced when the value is set. A value smaller
than the lower limit (No. 2-4-1-3) or a value larger than the maximum allowable range are not acceptable.
180.00
2-4-1-3
LRV
Change Analog Output 1 lower limit. A 4-mA output will be produced when the value is set. A value smaller
than the upper limit (No. 2-4-1-2) or a value larger than the maximum allowable range are not acceptable.
0.00000
2-4-1-4
Lowcut
Change Analog Output 1 low cutoff (%). When the low-flow cutoff is greater than the proportion of the
analog output where the upper limit (No. 2-4-1-2) is set at 100% and the lower limit (No. 2-4-1-3) is set at
0%, the analog output is clamped at 4 mA.
0.0
2-4-1-5
Added Damp
Change Analog Output 1 damping factor (sec). If Analog Output 1 fluctuates greatly, select a larger value.
For a fast response, select a lower value.
0.0
2-4-2-1
Assign
Change Analog Output 2 assignment (see
Analog Output Function, page 101
). If assignment is changed,
reconfigure upper limit (No. 2-4-2-2), lower limit (No. 2-4-2-3), low cutoff (No. 2-4-2-4) and damping factor
(No. 2-4-2-5) for optimum settings.
Density
2-4-2-2
URV
Change Analog Output 2 upper limit. A 20-mA output will be produced when the value is set. A value smaller
than the lower limit (No. 2-4-2-3) or a value larger than the maximum allowable range are not acceptable.
180.00
2-4-2-3
LRV
Change Analog Output 2 lower limit. A 4-mA output will be produced when the value is set. A value smaller
than the upper limit (No. 2-4-2-2) or a value larger than the maximum allowable range are not acceptable.
0.00000
2-4-2-4
Lowcut
Change Analog Output 2 low cutoff (%). When the low-flow cutoff is greater than the proportion of the
analog output where the upper limit (No. 2-4-2-2) is set at 100% and the lower limit (No. 2-4-2-3) is set at
0%, the analog output is clamped at 4 mA.
0.0
2-4-2-5
Added Damp
Change Analog Output 2 damping factor (sec). If Analog Output 2 fluctuates greatly, select a larger value.
For a fast response, select a lower value.
0.0
2-4-5-1
Weight
Change the Pulse Operating Mode to Weighted pulse output.
Weight
2-4-5-2
Frequency
Change the Pulse Operating Mode to Frequency pulse output.
2-4-3-1
Assign
Change Pulse Output 1 assignment (see
Pulse Output Function, page 97
). If assignment is changed,
reconfigure pulse weight (No. 2-4-3-2) for optimum settings.
Volume
Flow
2-4-3-2
Pulse Weight
Change the flow rate per unit of output pulse of Pulse Output 1.
1000.0
2-4-3-1
Assign
Change Pulse Output 1 assignment (see
Pulse Output Function, page 97
). If assignment is changed,
reconfigure frequency at full scale (No. 2-4-3-2), full-scale flow rate (No. 2-4-3-3) and low cutoff (No. 2-4-3-
4) for optimum settings.
Volume
Flow
2-4-3-2
Freq Factor
Change the maximum frequency of Pulse Output 1. An output is produced at the frequency (duty 50%) set
at full scale (No. 2-4-3-3). Configure this setting to match the measuring frequency range of the instrument
used for pulse output measurement.
1000.0
2-4-3-3
Rate Factor
Change Pulse Output 1 full-scale flow rate. An output is produced at the maximum frequency (No. 2-4-3-2)
when the preset flow rate is reached.
180.000
2-4-3-4
Lowcut
Change Pulse Output 1 low cutoff (%). When the proportion of the flow rate falls below the low cutoff where
the full-scale flow rate (No. 2-4-3-3) is set at 100%, the pulse output is clamped at 0.0.
0.0
2-4-4-1
Assign
Change Pulse Output 2 assignment (see
Pulse Output Function, page 97
). If assignment is changed,
reconfigure pulse weight (No. 2-4-4-2) for optimum settings.
Volume
Flow
2-4-4-2
Pulse Weight
Change the flow rate per unit of output pulse of Pulse Output 2.
1000.0
2-4-4-1
Assign
Change Pulse Output 2 assignment (see
Pulse Output Function, page 97
). If assignment is changed,
reconfigure frequency at full scale (No. 2-4-4-2), full-scale flow rate (No. 2-4-4-3) and low cutoff (No. 2-4-4-
4) for optimum settings.
Volume
Flow
2-4-4-2
Freq Factor
Change the maximum frequency of Pulse Output 2. An output is produced at the frequency (duty 50%) set
at full scale (No. 2-4-4-3). Configure this setting to match the measuring frequency range of the instrument
used for pulse output measurement.
1000.0
2-4-4-3
Rate Factor
Change Pulse Output 2 full-scale flow rate. An output is produced at the maximum frequency (No. 2-4-4-2)
when the preset flow rate is reached.
180.000
2-4-4-4
Lowcut
Change Pulse Output 2 low cutoff (%). When the proportion of the flow rate falls below the low cutoff where
the full-scale flow rate (No. 2-4-4-3) is set at 100%, the pulse output is clamped at 0.0.
0.0
Summary of Contents for CamCor CC001
Page 14: ...14 CamCor CT and PRO Series Hardware Manual Section 3 This page is left blank intentionally ...
Page 24: ...24 CamCor CT and PRO Series Hardware Manual Section 3 This page is left blank intentionally ...
Page 54: ...54 CamCor CT and PRO Series Hardware Manual Section 5 This page is left blank intentionally ...
Page 62: ...62 CamCor CT and PRO Series Hardware Manual Section 7 This page is left blank intentionally ...