ENGLISH
Pag. 12
D i s p l a y e d
name
Meaning
Description
THr1
Threshold 1 Displays and allows editing of the first alarm threshold
THr2
Threshold 2 Displays and allows editing of the second alarm threshold
THr3
Threshold 3 Displays and allows editing of the third alarm threshold
HYSt
Hysteresis
Displays and allows editing of hysteresis of the alarm thre-
sholds
rES
Reset
Reset of the Fault status
PAIr
Pairing
It allows the pairing between the sensing element and the
detector
VEr
Version
Detector firmware version
Adr
Address
To display and set the detectors’ address on the RS485 bus
bAUd
Baudrate
Displays and allows editing of the baud rate of the serial port.
List of available values: 9600, 115200
Depending on the detectors’ series, different menu entries are available. The following table
reports the available items per each type of detector
Table 3) Menu component available per each detector of SMART series
SUB-MENO
SMART series
3G
3R
3H
Serie LITE P
S
Password
Always requested at the start, the password is 1234 for all the gas detec-
tors.
Zero
Available for all detectors, if at least one sensor is connected
Span
Available for all detectors, if at least one sensor is connected
4-20 mA
x
Thr1
x 1
Thr2
x 1
x 1
x 1
x 1
x 1
x 1
Thr3
x 1
x 1
x 1
x 1
x 1
x 1
Hysteresis
x 1
x 1
x 1
x 1
x 1
x 1
Reset
x
x
x
x
x
x
Pairing
x
x
Version
x
x
x
x
x
x
Address
x[2]
x
x
x
x
x
Baudrate
V i s u a l i s e d
only[2]
x
x
x
Visualised
only
x
[1] To modify the alarm thresholds and the hysteresis value, the menu password is 5345.
[2] For old SMART 3G versions, the address and the baudrate options are not present.