Operator Manual
Page
22
of
40
P/N 1580281
SEC3120 Digital Transmitter
Sensor Electronics Corporation
Rev 10, 20150707
From the Initial/Top menu screen, cursor down to the Main Menu
and select ENTER.
Move the cursor down to the NETWORK menu and select
ENTER.
Select ENTER on NETWORK ID MENU.
If the ID mode (see Modbus settings
menu) is not
set to ‘Single’ and Sensor
Role (see Modbus settings menu) is not
set to ‘Single’, then you may change the
ID and Zone number for either sensor
one or two by choosing the sensor
number. Select ENTER on ‘FOR
SENSOR’ item, and use the UP/DN
arrows to change between ONE and
TWO. Otherwise, if ID mode or Sensor
Role is set to ‘Single’ all changes will be
made with SENSOR ONE displayed.
To set the ID of each sensor move the
cursor to ID and select ENTER. The IDs
of the sensors may be set in the range 1-
254, however they cannot be set to the
same value.
Note: Be sure to assign the sensor an ID number not
shared by any other sensors in
the HMI’s network.
To set the Zone of each sensor move the
cursor to ZONE and select ENTER. The
ZONE can be set in the range 1-254.
Scroll down and select ENTER on
PREVIOUS MENU to return to the
Network Menu Screen.
Scroll down to and select ENTER on PREVIOUS
MENU to return to the Main Menu.
ENTER on ‘SAVE CHANGES’ to return to the
Main Menu.
EJECT MEMORY CARD
ABORT WARMUP
INFO
* MAIN MENU
CALIBRATION
ALARM
RELAY
*
NETWORK
*
NETWORK ID MENU
MODBUS SETTINGS
PREVIOUS MENU
FOR SENSOR: ONE
ID
13
ZONE
3
*
PREVIOUS MENU
NETWORK ID MENU
MODBUS SETTINGS
*
PREVIOUS MENU
* SAVE CHANGES
ABORT CHANGES
*
FOR SENSOR: ONE/TWO *
ID
XXX
ZONE
YYY
PREVIOUS MENU
FOR SENSOR: ONE/TWO
ID
XXX
*
ZONE
YYY *
PREVIOUS MENU
FOR SENSOR: ONE/TWO
*
ID
XXX *
ZONE
YYY
PREVIOUS MENU