System test procedure
FlexPS Product Guide
Page 77
1.
Specify the type of alarm data network (Silver, Crossfire, or MX).
2.
For the Silver Star configuration, you must specify the IP address and the subnet mask and if
required, the gateway IP address for each processor.
3.
For the Crossfire network you must specify the baud rate (all devices on a Crossfire network
must communicate at the same baud rate).
4.
Save and download the configuration changes to the processor.
System test procedure
Once the system is calibrated and setup, you should conduct a series of tests to verify detection.
Run a UCM Response plot during the testing. Network based processors can be tested over the
network to verify network operation.
•
Cut detection
- Use the tap test, or weave a piece of scrap fence wire into the fabric of the
fence and cut the scrap wire. Test each zone in at least three separate locations.
At each location, tap the fence fabric, or cut the scrap wire, the number of times specified by
the cut Count parameter (default = 4). (Pass = alarm after Count setting is reached)
PASS ____ FAIL____
•
Climb detection
- Have a tester climb on the fence fabric for at least as long as the climb
Time parameter. Repeat the climb test in at least three locations. Use both a fast climb and a
stealthy climb to ensure detection (default = 2 seconds). (Pass = alarm after Time setting is
exceeded)
PASS ____ FAIL____
•
Fence lift detection
(Use care to ensure that the fence is not damaged during this test) -
Have a tester lift or pry up the bottom the fence fabric for a minimum of the time specified by
the Time parameter (depending on the amount of fence noise being generated, the test may
have to exceed the Time setting by several seconds). Repeat the lift test in at least three
locations (default = 2 seconds). (Pass = alarm after Time setting is exceeded)
PASS ____ FAIL____
•
Enclosure tamper
- Remove the cover from the enclosure. The DOOR OPEN LED (D1) turns
on, and the UCM Event log reports an Enclosure Tamper alarm. If a relay is configured to
activate for an enclosure tamper, the specified Relay should activate.
PASS ____ FAIL____
•
Cable supervision
- Use jumpers T12 (A-side) and T13 (B-side) to test for cable faults. If a
properly terminated sensor cable is connected to the A-side, place a shunt on T12. An A-side
supervision alarm should be declared. Remove the shunt from T12 and the A-side supervision
alarm should clear.
Note
For Silver Network based processors, there are two selectable
configurations based on media type. For EIA-422 and fiber optic cable,
select Silver Loop and for Ethernet communications select Silver Star.
Note
The following tests can be used to verify FlexPS system operation.
The tests are described in a generic manner, which does not take into
account site specific details (e.g., you can test the Audio output, only
if the Audio listen-in feature is setup at your site).