WIRING AND CONNECTIONS
Article type
RSTHF-2
RSTHG-2
VIN
18—34 VDC
18—34 VDC
15—24 VAC ±10%
GND
Ground
Common ground
*
AC ~
*
A
Modbus RTU (RS485), signal A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
Modbus RTU (RS485), signal /B
AO1
Analog / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
Analog / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO
Common ground
*
AO2
Analog / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
Analog / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO
Common ground
*
Connections
Spring contact terminal blocks, cable cross section: 1,5 mm
2
*
Caution: Never connect the common ground of G type articles to other devices powered by a DC voltage. If an AC power supply is used with a unit on a Modbus
network, the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT-USB-RS485 converter. This may cause permanent damage to the
communication semiconductors and / or the computer!
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the RSTHX-2 room sensor, read carefully
“Safety and
Precautions”
. Choose a smooth surface for installation (a wall, panel and etc.).
Follow these steps:
1.
Using a flat screwdriver, remove the front white cover by releasing the snap-fits
on its both sides (see
Fig. 1
Snap-fits release
).
2.
Insert the cables through the opening on the rear plate (See
Fig. 2
Mounting
dimensions
.)
3.
Using suitable fastening materials (not supplied), position the room sensor at
least 1,5 m from the floor. When planning the installation, allow enough clearance
for maintenance and service. Mount the sensor in a well-ventilated area. Mind
the correct mounting position and unit dimensions. See
Fig. 2
and
Fig. 3
.
Fig. 1 Snap-fits release
Fig. 2 Mounting dimension
2x Ø
6
59,8
9,
8
74,5
104,5
20
104,5
25,
6
70,
5
RSTHX-2
COMBINED TEMPERATURE AND RELATIVE
HUMIDITY ROOM TRANSMITTER