www.sentera.eu
MIW-SPS-EN-001 - 29 / 11 / 2018
7 - 12
back to the table of contents
5.
Customise the factory settings to the desired ones:
5.1
To select the analog output mode, use SW1 switch. (See
Fig. 5
Analog
output selection switch.
)
►
Select switch position 1 for 0—10 VDC mode of the analog output.
►
Select switch position 2 for 0—20 mA mode of the analog output.
►
Select switch position 3 for PWM (open collector).
Fig. 5 Analog output selection switch
5.2
То select the sensor range, use the jumpers indicated with 1, 2 and 3. (See
Fig. 6
Sensor range selection jumpers
and the enclosed information.)
5.3
Select the desired response time using the relevant jumpers (see
Fig. 7
Response time selection jumpers
). Use the enclosed information.
Fig. 6 Sensor range selection jumpers
Fig. 7 Response time selection jumpers
SPS-X-2K0
0—100 Pa
0—250 Pa
0—500 Pa
0—750 Pa
SPS-X-6K0
0—1.000 Pa
0—1.500 Pa
0—2.000 Pa
0—2.500 Pa
1 2 3
on on on
1 2 3
off on on
1 2 3
on off on
1 2 3
off off off
SPS-X-2K0
0—1.000 Pa
0- 2.000 Pa
-50—50 Pa
-100—100 Pa
SPS-X-6K0
0—3.000 Pa
0—4.000 Pa
0—5.000 Pa
0—6.000 Pa
1 2 3
on on off
1 2 3
off on off
1 2 3
on off off
1 2 3
off off off
0,5 sec
1 sec
(default)
2 sec
5 sec
4 5
on on
4 5
on off
4 5
off on
4 5
off off
6.
Close the enclosure and fix the cover.
7.
Connect the nozzles with the tubing.
8.
Switch on the power supply.
ATTENTION
If a G‑type article is using the same AC power supply source (transformer) as
F‑type article, a SHORT CIRCUIT may result when the power supply and analog
signal terminals are connected to the same common ground! In this case always
connect different article types to separate AC transformers or use the same
article version.
NOTE
For sensor calibration and Modbus register reset procedures refer to section
“
Operating instructions
”.
SPS
DIFFERENTIAL PRESSURE
TRANSMITTER