Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
24
Normal On/Off Screen
The
Normal Airflow
mode can be set to run during the
daytime i.e. from 6am to 11pm, the
Low Airflow
mode
will then run during the night from 11pm to 6pm.
The Normal On/Off screen enables you to set a time for
Normal to be activated for each day of the week.
You can set up to one
On
/
Off
time per day, If
On
and
Off
times are the same, the unit will not change speed.
On
time cannot be set earlier than a previous off time,
Likewise,
Off
time cannot be set earlier than a previous
On
time.
To set a weekly schedule:
Setting starts at
Mon
and uses
to show, by flashing,
which item is available for adjustment with the
and
buttons (a
→
b
→
c
→
d
→
e
→
Mon
and so on).
Mon 10:01 11:11
↑
↑
↑
↑
↑
a b c d e
When
Day
flashes, pressing
(> 2 sec) will copy
yesterday’s times to today.
Setting finishes when the last off minutes for
Sun
are
accepted, at which point the screen will now show
All Set
or holding the
button for 3 seconds.
Normal On Off
Mon 00:00 00:00
Normal On Off
All Set
Set Service No Screen
The Set Service No screen enables you to enter the
telephone number that should be called for service in
the event the unit fault.
Initially the screen is blank. Press
to get a
0
. Use
and
buttons to change between
0
and
9
(or
blank). Repeat until the number is entered. Finally,
select a blank and press
to finish. Maximum
16
digits.
Press and hold
for more than 2 seconds to clear
service number.
Set Service No
Internal Humidity Sensor Screen (if fitted)
The Humidity Sensor screen enables you to
switch the Sensor
On
and adjust the trigger point
between 60% and 70 %. (default setting 70%).
Humidity Sensor
Off
(
Day
)
(
Day
)
(
On
)
(
On
)
Repeat for
Off
Repeat for each
Day
.
Note: if same
times are used
on subsequent
days,
will
copy times
found.