Charging voltage adjustment interface. When the battery voltage
rises to the set voltage, it will maintain constant voltage charging.
Press and hold the MENU key to make the number flicker, and press
UP/DOWN to the required voltage, then long press MENU key to exit.
Charging current interface.
Discharging current interface.
Low-voltage recovery adjustment interface. When the controller cuts
off the load due to low-voltage, the load will be connected until the
battery voltage rises again to the set voltage. The setting method is
the same as above.
Low-voltage disconnect interface.When the battery voltage is lower
than this voltage, the controller automatically cuts off the load
output. The setting method is the same as the above.
Load working mode adjustment interface. The setting method is the
same as above. 24H means the controller will supply power to the
load for 24 hours. 0H means light-controlled mode. 1-23H means
after the light mode is on, you can adjust the time control from 1 to
23 hours to delay shutdown . The setting method is the same as above.
Battery type setting interface.
B01=LEAD-ACID, 12V B02=LITHIUM ION, 3x3.7V=11.1V
B03= LIFePO4, 4x3.2V=12.8V
The setting method is the same as above.
D2D trigger value (solar panel voltage)
When the load mode is set to light control or time control, the
controller will detect the voltage of solar panel to judge whether to
turn on the light. The higher the value is, the earlier the light will turn
on at dusk. The setting method is the same as above.