156
Appendices
-48 VDC Remote Power Manager
Installation and Operations Manual
LED Indicators
Outlets
Units are equipped with a status LED for each power receptacle. A lit/on LED indicates that power is being supplied at
the port and a darkened/off LED indicates that there is no power at the port.
Inlet Connections
The -48 VDC Remote Power Manager is equipped with two input blocks, each containing three clearly labeled
terminal positions. Connections are made using two-hole copper compression lugs for dual-stud blocks.
WARNING: Reverse polarity will damage the Remote Power Manager!
Verify proper polarity before connecting to a power source!
Two-hole Copper Compression Lugs
Cable
Stud
Color
Thomas&Betts Grainger
Size(AWG)
Size
Code
Model
Stock
#6 str.
¼”
Blue
54205
3LL91
#4 str
¼”
Gray
54206
3LL92
#2 str
¼”
Brown
54207
3LL93
#1 str
¼”
Green
54208
3LL94
Grainger catalog #390 (1999-2000)
Outlet Connections
The -48 VDC Remote Power Manager is equipped with four to
sixteen terminal outlet pairs each containing clearly labeled terminal
positions. Connections are made using two-hole copper
compression lugs for dual-stud blocks, and bare stripped wire for
high-density screw-down blocks. For the dual stud lugs, please
reference the table above.
-4
8
V
DC
GND
+R
T
N
- + - + - + - +
Screw -down Terminal
- + - +
Dual Stud Terminal