-48 VDC Remote Power Manager
Operations
69
Installation and Operations Manual
Operations Commands
Operations commands manage outlet states, provide information about the environment of the unit and control session
operations.
Turning outlets on:
The On command turns on one or more outlets. When the command completes, all outlets affected and their current
states will be displayed.
To turn outlets on:
At the Switched -48 VDC: prompt, type
on
, followed by an outlet name, and press
Enter
, or
Type
on
, followed by a group name, and press
Enter
, or
Type
on all
and press
Enter
.
Examples
The following command turns the second outlet on, using the outlet’s absolute name:
Switched -48 VDC: on .aa2<Enter>
The following command turns on all the outlets in the group named ServerGroup_1:
Switched -48 VDC: on ServerGroup_1<Enter>
Turning outlets off:
The Off command turns off one or more outlets. When the command completes, all outlets affected and their current
states will be displayed.
To turn outlets off:
At the Switched -48 VDC: prompt, type
off
, followed by an outlet name, and press
Enter
, or
Type
off
, followed by a group name, and press
Enter
, or
Type
off all
and press
Enter
Examples
The following command turns off the outlet named FileServer_1:
Switched -48 VDC: off FileServer_1<Enter>
The following command turns off all outlets:
Switched -48 VDC: off all<Enter>
Rebooting outlets:
The Reboot command reboots one or more outlets. This operation turns the outlet(s) off, delays for a user configurable
period and then turns the outlet(s) on. When the command completes, all outlets affected and their current states will
be displayed.
NOTE:
You will have to reissue the Status command to verify that the outlets have rebooted.
To reboot one or more outlets:
1.
At the Switched -48 VDC: prompt, type
reboot
, followed by an outlet name, and press
Enter
, or
2.
Type
reboot
, followed by a group name, and press
Enter
, or
3.
Type
reboot all
and press
Enter
.
Example
The following command reboots all the outlets in the group named ServerGroup_1:
Switched -48 VDC: reboot ServerGroup_1<Enter>