32
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Outlet State/Control State Field Values
Outlet State Control State
Description
On
On
Outlet is on
Off
Off
Outlet is off
Off
Pend On
Outlet is off and about to turn on in response to a sequence timer
Off
Reboot
Outlet is off and a Reboot action has been initiated
On
Idle On
A restart has occurred
– Last Control State has been maintained
Off
Idle Off
A restart has occurred
– Last Control State has been maintained
On
Wake On
A power-loss has occurred
– Wakeup State has been applied
Off
Wake Off
A power-loss has occurred
– Wakeup State has been applied
On/Wait
Off
Outlet state in transition
– Another query of outlet status is required
Off/Wait
On
Outlet state in transition
– Another query of outlet status is required
On/Error
(varies)
Error State
– Outlet should be off, but current is sensed at the outlet
Off/Error
(varies)
Error State
– Outlet should be on, but no current is sensed at the outlet
Off/Fuse
On
Outlet should be on, but a blown fuse has been detected
No Comm
(varies)
Communication to the outlet has been lost (control state will be applied when communication is
re-established)
Power Monitoring
Outlets
The
Power Monitoring > Outlets
page displays outlets by absolute/descriptive names and shows outlet status and
outlet load.
NOTE:
For DC products, only the outlet current measurement (in amps) is provided for outlet monitoring.
Monitor pages (like the Outlets page) refresh occasionally to reflect current status of the unit.