46
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Outlets
The
Configuration > Outlets
page configures options for all outlets and outlet shutdown settings.
Setting the outlet reboot delay:
Provide the reboot interval (in seconds) in the Reboot Delay field and click
Apply.
Editing the outlet descriptive name:
Click the
Edit
link in the Action column next to the outlet to be configured.
On the subsequent Outlets edit page, type a descriptive name. Up to 24 alphanumeric and other typed characters
(ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Click
Apply.
Changing the outlet wakeup state:
Click the
Edit
link in the Action column next to the outlet to be configured.
On the subsequent Outlet edit page,
select On, Off, or Last
from the Wakeup State drop-down menu, and click
Apply.
Setting the outlet post-on delay:
Click the
Edit
link in the Action column next to the outlet to be configured.
On the subsequent Outlet edit page, type the outlet post-on delay (in seconds) in the Post-On Delay field, and click
Apply.
Setting the outlet locked (no control) state:
The Outlet Locked feature protects against accidental switching off of critical equipment that should rarely, if ever, be
relay-controlled. The feature also prevents unused outlets from being turned on, for example, when a circuit is at
capacity and additional devices/loads should not be turned on.
Click the
Edit
link in the Action column next to the outlet to be configured.
On the subsequent Outlet edit page, check the Locked (No Control) checkbox to lock the outlet (or uncheck the box to
unlock the outlet), and click
Apply.
NOTE:
Outlets can only be locked and unlocked individually by outlet name; there is no global outlet lock/unlock command action.
When an outlet is configured into the locked state, the outlet will lock at its current control state (On or Off). The
outlet control state will then change to Locked On or Locked Off.
The locked control state (Yes or No) displays in the outlets list on the Outlets configuration page:
Control actions for a locked outlet will not be available in the web interface, and the outlet will not be affected by
group actions or Smart Load Shedding actions. SNMP and CLI control actions will be ignored for a locked outlet.