60
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Setting the number of RADIUS server retries:
The Set RADIUS Retries command specifies the number of times the authentication request is sent to the RADIUS
server. The CDU will attempt authentication with the primary server until the number of retries is reached, then will
attempt authentication with the secondary server. If the CDU does not receive a response from these attempts, the
authentication request will be rejected.
Setting the number of retries:
Type the number of retries in the Primary and/or Secondary Retries field and click
Apply.
The valid retries range is 0-10; default is 2.
SMTP/Email
The
Configuration > SMTP/Email
page allows the setup and maintenance of settings required to enable support for
both the Simple Mail Transfer Protocol (SMTP) and Email.
Enabling or disabling Email support:
Select
Enabled
or
Disabled
from the Email Notifications drop-down menu and click
Apply.
Setting the SMTP server address:
Enter the IP address or hostname in the SMTP Host field and click
Apply.
NOTE:
Both IPv4 and IPv6 formats are accepted in the Host field.
Changing the SMTP server port:
Enter the port number in the SMTP Port field and click
Apply.
Setting the SMTP authentication type:
NOTES:
SMTP authentication allows the mail client in the CDU to login to the mail server during the process of sending a mail. The mail server can
require this login to relay mail to another mail server.
Supported SMTP authentication types are: None (default, no SMTP authentication); Digest-MD5; CRAM-MD5; Login; and Plain. SMTP
authentication occurs with a configured username and password, or you can use the address in the ‘From’ Address field in place of the
username.
From the SMTP Authentication drop-down menu, select an authentication method. From the “with” drop-down menu,
select “SMTP Username” or “From Address”. Click
Apply.