-48 VDC Remote Power Manager
Operations
83
Installation and Operations Manual
Environmental Monitor Administration
Creating a descriptive Environmental Monitor name:
The Set Envmon Name command assigns a descriptive name to the integrated Environmental Monitor. This
descriptive name is displayed when the Evnmon command is issued.
To create an Environmental Monitor name:
At the Switched -48 VDC: prompt, type
set envmon name
followed by the absolute environmental monitor name,
then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed;
spaces are not allowed. Press
Enter
.
Example
The following command adds the descriptive name Florida_HQ_1to the Environmental Monitor:
Switched -48 VDC: set envmon name .a Florida_HQ_1<Enter>
Creating a descriptive temperature/humidity sensor name:
The Set Envmon THS Name command assigns a descriptive name to a temperature/humidity sensor. This descriptive
name is displayed when the Evnmon command is issued.
To create a temperature/humidity sensor name:
At the Switched -48 VDC: prompt, type
set envmon ths name
followed by the absolute name of the
temperature/humidity sensor, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33
to 126 decimal) are allowed; spaces are not allowed. Press
Enter
.
Example
The following command adds the descriptive name T/H2_Florida_HQ_1 to the second temperature/humidity sensor:
Switched -48 VDC: set envmon ths name .a2 T/H2_Florida_HQ_1<Enter>
Serial Port Administration
Creating a descriptive serial port name:
The Set Port Name command assigns a descriptive name to a serial port. You can use this name in commands that
require a port name as an alternative to using the port’s absolute name.
To create a port name:
At the Switched -48 VDC: prompt, type
set port name
followed by the absolute outlet name, then a descriptive name
of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed;
port names are not case sensitive. Press
Enter
.
Example
The following command adds the descriptive name Rack1 to Console port:
Switched -48 VDC: set port name console Rack1<Enter>
Setting the serial ports data-rate:
The Set Port Speed command sets the default data-rate for all serial ports.
Valid data-rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.
To set the serial port data-rate:
At the Switched -48 VDC: prompt, type
set port speed
, follow by the data-rate and press
Enter
.
Example
The following command sets the serial ports data-rate to 38400 BPS:
Switched -48 VDC: set port speed 38400<Enter>
Enabling or disabling active signal checking for serial connections:
The Set Port Dsrcheck command enables or disables active signal checking for serial connections to devices attached
to any of the available serial ports.
To enable or disable active signal checking for serial connections:
At the Switched -48 VDC: prompt, type
set port dsrcheck console
,
on
or
off,
and press
Enter
.