98
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Displaying FTP configuration information:
The Show FTP command displays all FTP configuration information.
FTP Host IP address
FTP Host username and password
Firmware filepath and filename
Configuration of automatic updates
To display FTP configuration information:
At the Switched -48 VDC: prompt, type
show ftp
and press
Enter
.
Example
The following command displays the FTP configuration information:
Switched -48 VDC: show ftp<Enter>
FTP Configuration
Host: 10.1.2.100
Username: djones
Password: *******
Directory: /firmware/7.0d
Filename: smCDU-v70d.bin
FTP Automatic Updates Configuration
Automatic Updates: Disabled
Scheduled Day: Everyday
Scheduled Hour: 1 PM
SNTP Administration
The firmware supports the use of a network time service to provide a synchronized time reference.
About Daylight Savings Time (DST)
Support for DST is disabled by default. When enabled, the date and time are automatically adjusted forward one hour
between the starting and ending dates and times (which can be configured).
NOTE:
If Daylight Savings Time (DST) is enabled, all system time displays will be shown with the current DST start/end date/time settings.
The default time zone is set for the United Stated until at least 2015.
The time zone format is:
mo.w.d/h:m:s
, as follows:
mo
= month from January to December (1-12)
w
= week number (1-4) or the last week (5)
d
= day of week from Sunday to Saturday (0-6)
h
= hour (0-23)
m
= minute (0-59)
s
= second (0-59)
Setting the SNTP server address:
The Set SNTP command sets the primary and secondary SNTP server addresses.
To set the SNTP server address:
At the Switched -48 VDC: prompt, type
set sntp
, followed by
primary
or
secondary
, and the SNTP server IP address
or hostname. Press
Enter
.
NOTES:
The primary/secondary IP addresses contact the SNTP server; these addresses are populated with the external NTP pool time zones
“2.pool.ntp.org” and “1.pool.ntp.org” as default for new CDUs that have not yet been time set.
Both IPv4 and IPv6 formats are accepted for primary/secondary IP address or hostname.
Examples
The following command sets the primary SNTP server address to 204.152.184.72:
Switched -48 VDC: set sntp primary 204.152.184.72<Enter>
The following command sets the secondary SNTP server address to cuckoo.nevada.edu:
Switched -48 VDC: set sntp secondary cuckoo.nevada.edu<Enter>