24
SESAMO
DUALCORE
DANGER: to carry out the LS procedure correctly, all the sensor and processor inputs
must have correct NO and NC values. Check the default values of the processor inputs in
the table and those of the inputs of the sensor in the manual of the sensor. If they are
incompatible, reprogram the specific input in the processor by following the procedure
described in this manual. If not, the safety devices could fail to work and the automatic
movement of the doors could cause serious injury or damage to persons or objects with
the risk of fatal lesions.
Activate the (LS) procedure as described below using the keys and display (fig
23.1):
1-
press the +/- keys on the display until the LS code appears then press ENT: the
display will show the code -- ;
2-
press again and hold the ENT key (about 5 seconds) until the counter displays
seconds from 60, 59, 58, ... to 0: the procedure has started correctly, release the
ENT key
3-
60 sec are available to: close the cover of the automated system, check that the
sensors are in the correct position, clear the detection area by removing any
obstacles under the sensors - note: it is possible to reset the count by pressing the
ESC key, and immediately passing to step 4
4-
after about 60 sec. the control unit acquires the sensors in about 10 sec - it is
possible to recognize the end of the LS procedure when the sensors remain in the
standby state
5-
open the cover and read the code on the display: if it is type S, proceed to point 6,
if it is type F flashing, proceed to point 7
6-
the S. code indicates which sensors have been detected according to the
correspondence of the table below; make sure that the indication on the display
corresponds to the sensors actually installed and if successful, press ENT to
confirm and save the configuration; otherwise press ESC, check the sensor wiring
and repeat the LS from point 1.
Report
Safe Open 2
Safe Open 1
Safe Close 2
Safe Close 1
S0
NO
NO
NO
NO
S1
NO
NO
NO
YES
S2
NO
NO
YES
NO
S3
NO
NO
YES
YES
S4
NO
YES
NO
NO
S5
NO
YES
NO
YES
S6
NO
YES
YES
NO
S7
NO
YES
YES
YES
S8
YES
NO
NO
NO
S9
YES
NO
NO
YES
SA
YES
NO
YES
NO
Summary of Contents for DUALCORE LH100
Page 1: ...LH100 LH140 RD100 ENGLISH AUTOMATED SYSTEMS FOR SLIDING DOORS INSTALLATION MANUAL ...
Page 44: ...44 SESAMO DUALCORE Fig A Fig B ...
Page 45: ...45 SESAMO DUALCORE Fig 1 ...
Page 46: ...46 SESAMO DUALCORE Fig 2 ...
Page 47: ...47 SESAMO DUALCORE Fig 3 ...
Page 48: ...48 SESAMO DUALCORE WARNING Exit way ONLY for RD100 Fig 4 ...
Page 49: ...49 SESAMO DUALCORE Fig 5 ...
Page 50: ...50 SESAMO DUALCORE Fig 5 A ...
Page 51: ...51 SESAMO DUALCORE Fig 6 Fig 7 ...
Page 52: ...52 SESAMO DUALCORE Fig 8 Fig 9 ...
Page 53: ...53 SESAMO DUALCORE Fig 9a Fig 10 ...
Page 54: ...54 SESAMO DUALCORE Fig 11 Fig 12 ...
Page 55: ...55 SESAMO DUALCORE Fig 13 Fig 14 Fig 15 ...
Page 56: ...56 SESAMO DUALCORE Fig 16 Fig 16a ...
Page 57: ...57 SESAMO DUALCORE Fig 17 Fig 17a ...
Page 58: ...58 SESAMO DUALCORE Fig 18 Fig 19 Fig 20 ...
Page 59: ...59 SESAMO DUALCORE Fig 21 Fuses 6 3A T J ...
Page 60: ...60 SESAMO DUALCORE Fig 22 ...
Page 61: ...61 SESAMO DUALCORE Fig 23 1 Fig 23 2 ...
Page 62: ...62 SESAMO DUALCORE Fig 24 PARAMETER 30 1 ...
Page 63: ...63 SESAMO DUALCORE Fig 25 PARAMETER 30 1 Exit way ...
Page 64: ...64 SESAMO DUALCORE Fig 25 A ...
Page 65: ...65 SESAMO DUALCORE Fig 26 ...
Page 66: ...66 SESAMO DUALCORE Fig 27 PARAMETER 31 1 ...
Page 67: ...67 SESAMO DUALCORE Fig 28 PARAMETER 31 0 ...
Page 68: ...68 SESAMO DUALCORE Fig 29 ...
Page 69: ...69 SESAMO DUALCORE Fig 30 Fig 31 ...
Page 71: ...71 SESAMO DUALCORE Fig 33 ...
Page 72: ...72 SESAMO DUALCORE Fig 34 ...