Battery Management

To maintain the battery in a good state of health an intelligently controlled charging algorithm is 
used.  The purpose is to ensure that the correct voltages are applied to the battery terminals at the 
appropriate times throughout it’s usage cycle.  
To prevent corrosion on the battery positive plate due to continuous float charging current (VFloat 
= 13.65V), the unit utilises a storage mode voltage (VStore = 13.25V) when no activity on the 
battery is detected. This extends the battery life. During store mode, the unit exits to boost mode 
(VBoost = 14.05V) for 15 minutes every 24hrs to maintain charge in the battery. If battery activity 
is detected during store mode it exits automatically into float mode.
For any decision making involving the “loss of mains” detection there is a 2 minute mains debounce 
period where there must be no mains signal present on the mains detect input for the “no mains” 
signal to be valid.
A detailed description of the operational requirements for the charging algorithm is described 
below:

Present Output 

Set Voltage

Conditions Required to 

Enter Operational State

Operational State

New Output Set 

Voltage

N/A

Microcontroller first power 
up.

Initial application of power 
to the microcontroller 
either from 240VAC mains 
input or connection of a 
battery to the battery input 
(Includes Auxiliary power).

Vfloat

Vfloat (No Mains 
Input)

Mains input detected after 
loss of mains for less than 
1 hour.

Float charging mode with 
mains input voltage 
detected (set 24 hour 
timer).

Vfloat

Vboost

Mains input voltage was 
detected for more than 15 
minutes.

Float charging mode with 
mains input voltage 
detected (set 24 hour 
timer).

Vfloat

Vfloat

No mains input voltage is 
detected.

Float charging mode with 
no mains input voltage 
detected (set 1 hour timer).

Vfloat (No 
mains input)

Vstore

No mains input voltage is 
detected.

Float charging mode with 
no mains input voltage 
detected (set 1 hour timer).

Vfloat (No 
mains input)

Periodic_Vboost

No mains input voltage is 
detected.

Float charging mode with 
no mains input voltage 
detected (set 1 hour timer).

Vfloat (No 
mains input)

Page 9 of 11

Issue F

Summary of Contents for ST20-II

Page 1: ...of the load from an external 13 8V DC power source The units are fully enclosed ready for direct wall mounting All connections are at the rear of unit providing convenient wiring and installation Use...

Page 2: ...battery will be charging at 0 8A When the battery voltage is sufficient 10 5V for first power up 11 5V and 11 7V for subsequent reconnection with and without mains respectively the LVD will connect th...

Page 3: ...ll shut down It will attempt to automatically restart every 5 seconds until such case that the fault is removed Fusing Each load circuit and the battery have been fused to provide fault protection and...

Page 4: ...shut down A minimum ventilation of 20 000mm2 to the outside world must be provided CAUTION Do not install unit in same compartment as batteries or flammable material such as petrol Ensure that the ins...

Page 5: ...ating QC connector suitable for cable size Connector pin out is shown below Cabling sizes DC cables must be sized to carry the maximum full load current and not exceed the system volt drop requirement...

Page 6: ...r supply terminal or negative chassis ground If battery is connected to chassis ensure a connection exist from chassis to Batt VE terminal of power supply Battery Disconnection Procedures Battery shou...

Page 7: ...servicing a battery disconnect the power supply Batteries are electrically alive at all times and must be treated with extreme caution They can supply high short circuit currents even if they appear d...

Page 8: ...tion 17V Over Current Protection ST20 II 20A to 25A load battery current ST35 II 35A to 38A load battery current Battery Current Limit 10A 1A ST20 II 15A 1A ST35 II Battery Connect Disconnect Connect...

Page 9: ...A detailed description of the operational requirements for the charging algorithm is described below Present Output Set Voltage Conditions Required to Enter Operational State Operational State New Ou...

Page 10: ...oost charging mode active after resumption of mains input supply set 15 minute boost timer Vboost Vboost No mains input voltage is detected Boost charging mode while no mains is detected Vboost No Mai...

Page 11: ...or devices in close proximity 3m and as such do not guarantee that the power supply will not cause interference with devices such as TV s or radios The ST20 II 35 II have been designed with equipment...

Reviews: