ADM adapter
The adapter has been designed to efficiently carry out the sensitivity levels management functions sometimes ne-
cessitated by ambient disturbances found in buildings protected by the
ARDEA, BOOMERANG and ECO
range
of fire detectors.
SETRONIC Verona wishes all its customer to have maximum performance from our detectors through the use of
the ADM, which is a simple, economic and practical device that can be used by anyone in association with an or-
dinary multimeter.
WARNING NOTES
• Keep the ADM with care and check its connectors and jack plug each time before using it.
• Check the internal battery. The low battery indictaor
2
must be off. Replace the battery if it is on.
• Switch the ADM off after use each time to stop the battery discharging.
PRELIMINARY OPERATIONS
a) Carry out the detector centring procedure as shown in the manual provided.
b) Plug the ADM jack plug into the detector's socket.
c) Insert the Red (+)
5
and black (-)
4
plugs into your multimeter.
d) Set the multimeter as Voltmeter in scale, e.g. 2V.
e) Switch the ’ADM on with the
3
ON/OFF switch and check that the Green Led
1
is on.
f) Check that the visual field of the detector is free, taking care that the ADM's jack cable does not go in front of
the detector optic as this will falsify the result.
g) Wait at least un minute before taking the DETECTOR reading.
Set
switch
6
to
DETECTOR.
Read
the
peak
values
at
the
environment's
most
active
times
(
e.g.
by switching on and off the lighting, heating/air conditioning systems, any steam or heat-producing machi-
nes etc.).
If the installation position for the detector is right, the DETECTOR readings will stay around an average of between
a negative value
≥
30 mV and a positive value
≤
70 mV.
WARNING!
As regards this average, you must also remember the peak values!
ARDEA RANGE ( mod. ARDEA S/2, ARDEA SF, ARDEA SF Dust)
1.
Read the DETECTOR value by setting switch
6
to the DETECTOR position
2.
Read the SMOKE threshold by setting switch
6
to the SMOKE position
3.
Read the FIRE threshold by setting switch
6
to the FIRE position (only SF models)
ARDEA EExd / IP65 model. S
1.
Read the DETECTOR value, setting switch
6
to the DETECTOR position
2.
Read THRESHOLD 1 by setting switch
6
to the FIRE position
3.
Read THRESHOLD 2 by setting switch
6
to the SMOKE position
BOOMERANG RANGE (mod. BOOMERANG S, BOOMERANG SF)
1.
Read the DETECTOR value by setting switch
6
to the DETECTOR position
2.
Read the FIRE threshold by setting switch
6
to the FIRE position (only SF models)
3.
Read the SMOKE threshold by setting switch
6
to the SMOKE position
ECORANGE (mod. ECO50, ECO80, ECO 100)
1.
Read the DETECTOR value, setting switch
6
to the DETECTOR position
N.B.
with switch
6
in the FIRE or SMOKE position, the value displayed is always that of the DETECTOR!
It is advisable to
refer to the instruction manual
for the specific detector for the
correct threshold
settings
in relation to the ambient disturbance value measured with the ADM.
The instruction manuals for the individual detectors are available in PDF format and can be downloaded
from the
Technical Area
of the Website
www.setronicverona.com
, after you logged into the
Reserved
Area
.
SETRONIC Verona
ADM Adapter
Rev. 00