MAIN CALIBRATION PROCEDURES
1.
Enter menu:
ž
from the main screen, press OK;
ž
enter the password, using the direction buttons
„‚ƒ
; press OK;
2.
Set up detection lines:
ž
press
„
or
ƒ
until you get to < System Setup >; press OK;
ž
press
or
‚
to edit the number of the detection lines; press OK;
ž
press
or
‚
to change the delay time for fault outputs; press OK;
ž
press
or
‚
to change the configuration of fault outputs; press OK;
ž
press
or
‚
to set the <Com Line> configuration; press OK;
ž
press OK to skip debug function.
3.
First calibration of the detection lines (with mechanical adjustment of detectors):
ž
press
„
or
ƒ
until you get to < AUTO Adjust. >; press OK;
ž
press
or
‚
to change the number of the detection line to be worked on; press OK;
ž
wait until the TX value stabilises and press OK;
ž
the value of the RX must be about 100%
(see note at pag. 72)
ž
press OK to confirm the setting.
4.
Calibration of detection lines (with the detectors already previously installed):
ž
press
„
or
ƒ
until you get to < AUTO Adjust. >; press OK;
ž
press
or
‚
to change the number of the detection line to be worked on; press OK;
ž
wait until the TX value stabilises and press OK;
ž
the value of the RX must be about 100%
(see note at pag. 72)
ž
press OK to confirm the setting.
5.
Adjustment of detection line sensitivity:
ž
press
„
or
ƒ
until you get to < sensitivity >; press OK;
ž
press
or
‚
to change the number of the detection line to be worked on; press OK;
ž
read the Detec value to quantify environmental disturbances;
ž
press
or
‚
to change the smoke threshold value (the value of the highest
disturbance value seen by Detec shall be less than the threshold setted) ; wait
for 2 sec and press OK;
ž
read the Detec value to quantify environmental disturbances;
ž
press
or
‚
to change the fire threshold value (the value of the highest
disturbance value seen by Detec shall be less than the threshold setted);
ž
wait for 2 sec and press OK to confirm the setting.
ENGLISH
64
Mod. MII
rev. 01
SETRONIC Verona