After the alarm test
the
detector does not
immediately reset
from the
“
Reset Alarm
” menu.
Maintenance
signal
Sporadic
fault
signals
Ø
The detector is still responding to the
alarm event. Wait around 1 minute and
then repeat the reset from “Reset Alarm
menu. If the operation is carried out after
a test fire , wait for the evacuation of the
smoke, and then carry out the reset.
Ø
Check that frontal part is clean. Possible
deterioration of the signal received due
to deposits on the front of the detector or
to misalignment beyond tolerance
levels. The signal levels received can be
checked with the “adjust” menu (if the
reading is below 50% then maintenance
is necessary). If the problem comes
back, check physical alignment of the
two units.
Ø
Indication of Maintenance request are
possible also for the presence of steam,
fog or dust in environment; the same
could happens with ice on optical frontal
part.
Ø
Read the signal received value using the
< Adjustment > menu. If the figure is
between 104% and 107% lower the
Transmitter level to 100%. If necessary
check the rigidity of the structure to
which the barrier is fastened or the
fastening itself.
Ø
It is also possible that air in the
environment is cleaner that when the
calibration was carried out, so the signal
received is greater with a consequent
saturation signal. In this case adjust the
t r a n s m i t t e r b y m e a n s o f t h e
<Adjustment> menu until you reach a
reading of 100%.
PROBLEM
CHECK AND REMEDY
TROUBLE SHOOTING
ENGLISH
88
Mod. MII
rev. 01
SETRONIC Verona