Operating Instructions – MOVIGEAR
®
classic
52
5
Electrical installation
5.1
Equipotential bonding
Regardless of the PE connection, it is essential that
low-impedance,
HF-capable
equipotential bonding
is provided (see also EN 60204-1 or DIN VDE 0100-540):
•
Establish a connection over a wide surface area between the drive unit and the
mounting rail.
•
To do so, use a ground strap (HF litz wire), for example, to connect the drive unit
and the grounding point of the plant.
[3]
[1]
[2]
21493716107
[1]
Conductive connection over a large area between drive unit and mounting plate
[2]
PE conductor in the supply system cable
[3]
EMC-compliant equipotential bonding, for example using a ground strap (HF litz
wire)
25805134/EN – 07/2018