5
Electrical installation
Installation instructions
Operating Instructions – MOVIGEAR
®
classic
57
5.3.4
Notes on PE connection
WARNING
Electric shock due to incorrect connection of PE.
Severe or fatal injuries.
•
The permitted tightening torque for the screw is 2.0 – 2.4 Nm.
•
Observe the following notes regarding PE connection.
Prohibited assembly
Recommendation:
Assembly with forked cable lug
Permitted for all cross sections
Assembly with solid connecting
wire
Permitted for cross sections up
to max. 2.5 mm
2
[1]
M5
22904959499
2.5 mm²
M5
22904948235
[1] Forked cable lug suitable for M5 PE screws
25805134/EN – 07/2018