11
Supplementary field distributor startup information
MOVIMOT® inverter integrated in field distributor
Manual – PROFINET IO Interfaces, Field Distributors
141
11.5
MOVIMOT
®
inverter integrated in field distributor
MOVIMOT®
inverter
integrated
in field
distributor
The following chapter describes the differences in the use of the MOVIMOT
®
inverter
integrated in the field distributor compared to use when it is integrated in the motor.
11.5.1
Different factory settings for MOVIMOT
®
integrated in the field distributor
Note the changes to the factory settings (in bold) when using MOVIMOT
®
integrated in
Z.7., Z.8. or Z.9 field distributors:
S1 DIP switch
S1
1
2
3
4
Meaning
RS485 address
2
0
2
1
2
2
2
3
MOVIMOT
®
1
ON
1
1
1
1
OFF
0
0
0
0
MOVIMOT
®
2
1)
ON
1
1
1
1
OFF
0
0
0
0
MOVIMOT
®
3
1)
ON
1
1
1
1
OFF
0
0
0
0
1) Only for Z.9. field distributor.
S1
5
Motor
protec-
tion
6
Motor
performance
level
7
PWM
frequency
8
No-load
damping
Meaning
ON
Off
Motor one stage
smaller
Variable
(16, 8,
4 kHz)
On
OFF
On
Adjusted
4 kHz
Off
Setpoint poten-
tiometer f1
10
0
100
2
75
25
50
10
f
1
[1]
1
2
3 4
5
6 7
8 9
f1
Hz
9007200441723659
[1] Factory setting
All other settings are identical to the settings for a MOVIMOT
®
drive with integrated in-
verter. See MOVIMOT
®
operating instructions.
22870857/EN – 12/2016