Installation instructions
Electrical Installation
5
Electrical Installation
5.1
Installation instructions
5.1.1
Supply system connection
• The rated voltage and frequency of the MOVIMOT
®
inverter must correspond to the
data for the power supply system.
• Install line fuses at the beginning of the power supply cable behind the supply bus
junction, see F11/F12/F13 in chapter "Connection of MOVIMOT
®
drive".
Use only D, D0 or NH fuses, or circuit breakers for F11/F12/F13. Select the fuse size
according to the cable cross section.
• SEW-EURODRIVE recommends using earth-leakage monitors with pulse code
measuring in voltage supply systems with a non-grounded star point (IT systems).
The use of such devices prevents the earth-leakage monitor mis-tripping due to the
earth capacitance of the inverter.
• Cable cross section: according to input current I
line
for rated power (see chapter
"Technical Data" in the operating instructions).
5.1.2
Permitted cable cross section of MOVIMOT
®
terminals
Power terminals
Observe the permitted cable cross sections for installation:
Control terminals
Observe the permitted cable cross sections for installation:
Power terminals
Cable cross section
1.0 mm
2
- 4.0 mm
2
(2 x 4.0 mm
2
)
AWG17 – AWG12 (2 x AWG12)
Conductor end sleeves
•
For single assignment:
Only connect single-wire conductors or flexible conduc-
tors with conductor end sleeve (DIN 46228, material E-
CU) with or without insulating shrouds
•
For double assignment:
Only connect flexible conductors with conductor end
sleeve (DIN 46228-1, material E-CU) without insulat-
ing shrouds
•
Permitted length of the conductor end sleeve: At least 8
mm
Control terminals
Cable cross section
0.5 mm
2
– 1.0 mm
2
AWG20 – AWG17
•
Single-wire conductor
(bare wire)
•
Flexible conductor
(bare litz wire)
•
Conductor with end sleeve
Without insulating shrouds
•
Conductor with end sleeve
With insulating shrouds
0.5 mm
2
– 0.75 mm
2
AWG20 – AWG19
Conductor end sleeves
•
Only connect single-wire conductors or flexible conduc-
tors with or without conductor end sleeve (DIN 46228,
material E-CU)
•
Permitted length of the conductor end sleeve: At least 8
mm