5
Electrical installation
Installation instructions
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
21
5.2.2
Permitted cable cross section of the MOVIMOT
®
terminals
Power terminals
Observe the permitted cable cross sections for installation:
Power terminals
Cable cross section
1.0 mm
2
– 4.0 mm
2
(2 x 4.0 mm
2
)
AWG17 – AWG12 (2 x AWG12)
Conductor end sleeves
•
For single assignment:
Connect only single-wire conductors or flexible
conductors with conductor end sleeves (DIN
46228, material E-CU)
with or without plastic
collars
.
•
For double assignment:
Connect only flexible conductors with conductor
end sleeve (DIN 46228-1, material E-CU)
with-
out plastic collar
.
• Permitted length of the conductor end sleeve: at
least 8 mm
24 V AUX-PWR terminals
Observe the permitted cable cross sections for installation:
24 V AUX-PWR terminals ("24V"/"
⍊
")
Cable cross section
0.2 mm
2
– 2.5 mm
2
AWG24 – AWG14
Control terminals
Observe the permitted cable cross sections for installation:
Control terminals
Cable cross section
• Single-wire conductor
(bare wire)
• Flexible conductor
(bare litz wire)
• Conductor end sleeve
without
plastic collar
0.5 mm
2
– 1.0 mm
2
AWG20 – AWG17
• Conductor end sleeve
with
plastic collar
0.5 mm
2
– 0.75 mm
2
AWG20 – AWG19
Conductor end sleeves
• Connect only single-wire conductors or flexible
wire conductors
with or without
conductor end
sleeve (DIN 46228, material E
‑
CU).
• Permitted length of the conductor end sleeve: at
least 8 mm
21328994/EN – 11/2014