Explanation of the parameters
Parameterization of MOVIPRO
®
P83x Fault
responses
The following responses can be programmed:
P830 Response to
"External fault"
Factory setting: Emergency stop/fault
The error is only triggered in the ENABLED inverter status. P830 programs the fault re-
sponse which is triggered by an input terminal programmed to "/EXT. ERROR".
Response
Description
No response
No error is displayed and no error response is triggered. The signaled error is
ignored.
Display fault
The fault is displayed (in the 7-segment display and in MOVITOOLS
®
Motion-
Studio). The unit performs no other fault responses. The fault can be reset (ter-
minal, fieldbus, auto reset).
Immediate stop/fault
The inverter switches off immediately and an error is signaled. The output stage
is inhibited and the brake is applied. The ready signal is revoked. A restart is
only possible after an error reset has been performed during which the inverter
is reinitialized.
Emergency stop/fault
The drive is braked with the set emergency stop ramp t14/t24 (page 94). Once
the stop speed is reached, the output stage is inhibited and the brake is applied.
The error is signaled immediately. The ready signal is revoked. A restart is only
possible after an error reset has been performed during which the inverter is
reinitialized.
Rapid stop/fault
The drive is braked with the set stop ramp t13/t23 (page 94). Once the stop
speed is reached, the output stage is inhibited and the brake is applied. The
error is signaled immediately. The ready signal is revoked. A restart is only pos-
sible after an error reset has been performed during which the inverter is reini-
tialized.
Immediate stop/warning
The inverter switches off immediately and an error is signaled. The output stage
is inhibited and the brake is applied. The ready signal is not revoked. The drive
restarts without a unit re-initialization if the error is rectified by an internal proce-
dure or by an error reset.
Emergency stop/warning
The drive is braked with the set emergency stop ramp t14/t24 (page 94). Once
the stop speed is reached, the output stage is inhibited and the brake applied.
The error is signaled immediately. The ready signal is not revoked. The drive
restarts without a unit re-initialization if the error is rectified by an internal proce-
dure or by an error reset.
Rapid stop/warning
The drive is braked with the set stop ramp t13/t23 (page 94). Once the stop
speed is reached, the output stage is inhibited and the brake applied. The error
is signaled immediately. The ready signal is not revoked. The drive restarts with-
out a unit re-initialization if the error is rectified by an internal procedure or by an
error reset.