Manual – MOVIPRO® SDC with DeviceNet Interface
33
5
Configuration examples in RSLogix 5000
Configuration and Startup on the DeviceNet Fieldbus
5. Set the target unit in the "Communication" tab page:
The path consists of:
• Name of the scanner (e. g. DNet_Scanner)
• 2 (always 2)
• Slave address (e. g. 11)
6. After downloading the changes to the PLC, the index of the parameter to be read can
be entered at
ReadParameterRequest.Index
. Changing the
ReadParameterStart
control bit to "1" executes the read command once:
On response to the read request,
ReadParameterResponse.Index
should indicate
the read index and
ReadParameterResponse.Data
should contain the read data. In
this example, the timeout delay of the MOVIPRO
®
(index 8606) set by the scanner
has been read (012Chex = 0.3 s).