48
Manual – MOVIPRO® SDC with DeviceNet Interface
6
Return codes of the parameterization via explicit messages
DeviceNet Operating Characteristics
6.3.5
MOVILINK
®
-specific return codes
The following table lists the MOVILINK
®
protocol-specific error messages and their cod-
ing in the DeviceNet response telegram.
General
error code
[hex]
Additional
code
[hex]
Error name
Corresponds
to
MOVILINK
®
Error code
[hex]
Corresponds to
MOVILINK
®
Additional code
[hex]
0xD0
0xF0
Unknown error
0x05
0x00
0xF1
Illegal Service
0x01
0xF2
No Response
0x02
0xF3
Different Address
0x03
0xF4
Different Type
0x04
0xF5
Different Index
0x05
0xF6
Different Service
0x06
0xF7
Different Channel
0x07
0xF8
Different Block
0x08
0xF9
No Scope Data
0x09
0xFA
Illegal Length
0x0A
0xFB
Illegal Address
0x0B
0xFC
Illegal Pointer
0x0C
0xFD
Not enough memory
0x0D
0xFE
System Error
0x0E
0xD1
0xF0
Communication does not exist
0x0F
0xF1
Communication not initialized
0x10
0xF2
Mouse conflict
0x11
0xF3
Illegal Bus
0x12
0xF4
FCS Error
0x13
0xF5
PB Init
0x14
0xF6
SBUS – Illegal Fragment Count
0x15
0xF7
SBUS – Illegal Fragment Type
0x16
0xF8
Access denied
0x17
0xF9 – 0xFE
Not used