Manual – MOVIPRO® SDC with DeviceNet Interface
109
10
Explanation of the parameters
Parameterization of MOVIPRO
®
10.4.8 P7xx Control functions
All settings with regard to the fundamental control properties of the inverter are defined
within parameter group 7xx. These are all functions that the inverter executes automat-
ically when activated. They affect how the inverter responds in certain operating modes.
P70x Operating modes
P700/P701 Oper-
ating mode 1/2
This parameter is used to set the basic operating mode of the inverter for parameter sets
1 and 2. This includes in particular the definition of the motor system, encoder feedback
and corresponding control functions. When the inverters are delivered, their parameters
are set to the specific motor which matches the power of the inverter.
IPOS input
Function depending on the application module
Reference cam
Not activated
Activated
no
yes
Start reference
travel
-
Start referencing for
the application
module
no
yes
Mains On detec-
tion
see P521 (page 105)
Ext. signal "Mains
on"
yes
yes
P52x
(page 105)
/Vibration warning
Vibration sensor sig-
nals warning
Vibration sensor
does not signal
warning
yes
yes
/Vibration fault
Vibration sensor
reports fault
Vibration sensor
does not report fault
yes
yes
/Oil aging warning
Oil aging sensor sig-
nals warning
Oil aging sensor
does not signal
warning
yes
yes
/Oil aging fault
Oil aging sensor sig-
nals fault
Oil aging sensor
does not signal fault
yes
yes
/Oil aging overtem-
perature
Oil aging sensor
reports overtempera-
ture
Oil aging sensor
does not signals
overtemperature
yes
yes
Oil aging ready
signal
Oil aging sensor is
not ready for opera-
tion
Oil aging sensor is
ready for operation
yes
yes
Brake wear moni-
toring
Brake is worn
Brake is ok
yes
yes
1) Important for operating modes with encoder feedback: The parameter set must not be changed more often
than every two seconds.
Function
Effect when
Effective with
inverter status
Fac-
tory-
set to
see
"0" signal
"1" signal
Inhib-
ited
Enabled
INFORMATION
When using incremental encoders (resolver, push-pull TTL, RS422, sin/cos,
HIPERFACE
®
single-turn), changing the parameter set invalidates the positions H510
and H511. If a valid position is to be maintained after the parameter set has been
changed, an absolute encoder (SSI, HIPERFACE
®
multi-turn) must be used.