7
Electrical installation
Terminal assignment
Manual – MOVISAFE
®
CS..A Safety Card (Version 2)
50
7.3
Terminal assignment
Description
LED/
Terminal
Function
F-RUN LED
F-ERR LED
F-RUN LED
F-ERR LED
The LEDs indicate the status of the CS..A
safety card (see chapter "Diagnostics").
XS: Slot for safety key
XS
Slot for safety key
X17 (D-sub DA-15):
Connecting second encoder (CSS31A
and CSB31A only)
Not used for functional safety.
X17:1 – 15
Assignment depends on connected en-
coder
(see manual "MOVIDRIVE
®
modular sys-
tem/technology – CES11A multi-encoder
card").
X60: Connection of digital inputs (plug-
in spring-loaded terminals)
X60:1 F-DI00
Safe digital input F-DI00.
X60:2 F-DI01
Safe digital input F-DI01.
X60:3 GND
Reference potential for safe inputs/outputs.
X60:4 GND
Reference potential for safe inputs/outputs.
X60:5 F-DI02
Safe digital input F-DI02.
X60:6 F-DI03
Safe digital input F-DI03.
X60:7 GND
Reference potential for safe inputs/outputs.
X60:8 GND
Reference potential for safe inputs/outputs.
X60:9 F-SS0
DC 24 V sensor voltage supply for safe di-
gital inputs F-DI00 and F-DI02.
X60:10 F-SS1
DC 24 V sensor voltage supply for safe di-
gital inputs F-DI01 and F-DI03.
X60:11 F-DO00_M
Safe digital output F-DO00_M (not with
CSB21A).
X60:12 F-DO00_P
Safe digital output F-DO00_P (not with
CSB21A).
X60:13 F-DO01_M
Safe digital output F-DO01_M (not with
CSB21A).
X60:14 F-DO01_P
Safe digital output F-DO01_P (not with
CSB21A).
7.4
Safe disconnection
The jumper plug X6 at the inverter must be removed if a MOVISAFE
®
CS..A safety
card is installed in the MOVIDRIVE
®
modular/system/technology. No external voltage
must be connected to the X6 connection of the inverter.
7.5
Safe digital inputs (F-DI.)
The safe digital inputs (F-DI.) are connected at terminal X60. The following sections
explain and describe the permitted connection options.
28482271/EN – 03/2019