3
System description
SBus installation of several devices
Product Manual – MOVITRANS
®
TES31A Decentralized Supply Unit Synchronization
15
The total cable length permitted for SBus communications depends on the set SBus
baud rate:
SBus baud rate
Total cable length
125 kBd
500 m
250 kBd
250 m
500 kBd (standard)
100 m
1000 kBd
25 m
The following figure shows the signal diagram for the SBus communications:
TES31-Master
X4108
X4101
TES31-Slave 1
X4108
X4101
TES31-Slave N
X4108
X4101
...
32447182603
29190657/EN – 04/2020