Parameter setting
Startup
Activating programming mode
To change from normal operation to parameter setting mode, press button 2 (CONFIG)
on the back of the read head.
To activate parameter setting mode:
1. Press button 2 (CONFIG) for longer than 2 seconds.
The yellow "OUT1" LED flashes.
2. For final activation, hold the "ENABLE" code in front of the camera system of the read
head.
If the "ENABLE" activation code is detected, the green "PWR/ADJ/ERROR/NO
CODE" LED flashes for 1 second. If the activation code is not detected, the
"PWR/ADJ/ERROR/NO CODE" LED lights up red for 2 seconds.
Parameter setting
Place the parameterization code in the field of view of the camera module.
If the parameterization code is detected, the green "PWR/ADJ/ERROR/NO CODE" LED
lights up for 1 second. If the parameterization code is not detected, the "PWR/ADJ/ER-
ROR/NO CODE" LED lights up red for 2 seconds.
Exiting parameter
setting mode
To save the configuration, hold the "STORE" code in front of the camera system of the
read head.
If the "STORE" memory code is detected, the green "PWR/ADJ/ERROR/NO CODE"
LED lights up for 1 second. The parameters are stored in the non-volatile memory of the
read head, and parameter setting mode is terminated. You have now successfully set
the parameters for the read head. If the memory code is not detected, the
"PWR/ADJ/ERROR/NO CODE" LED lights up red for 2 seconds.
INFORMATION
You have to start external parameterization of the read head using code cards within
the first 10 minutes after activation of the read head. A time lock disables the read
head when this time has elapsed. The time lock remains inactive during the parameter
setting process. The time lock only disables the read head if no parameters are set for
more than 10 minutes.
If you press a button when the time lock is enabled, then all LEDs flash for 2 seconds.
INFORMATION
Briefly pressing button 2 (CONFIG) in parameter setting mode immediately exits this
mode. Any parameter changes you made but have not saved will be discarded. The
read head continues to operate with the last valid parameters that were saved.