Manual – DFD11B DeviceNet Fieldbus Interface
19
4
Setting the DIP switches
Assembly and Installation
4.8
Setting the DIP switches
Setting the MAC-
ID
The MAC-ID (
M
edia
A
ccess
C
ontrol
Id
entifier) is set on the DFD11B option card with
DIP switches S1-NA0 ... S1-NA5. in a binary coded manner. The MAC-ID represents the
node address of the DFD11B. The DFD11B supports the address range 0 ... 63.
Setting the baud
rate
The baud rate is set with DIP switches S2-DR0 and S2-DR1.
Setting the pro-
cess data length
Up to ten data words (DFD11B in MOVIDRIVE
®
B) and up to 24 data words (DFD11B
as gateway in MOVITRAC
®
B or UOH11B) can be exchanged between the DeviceNet
master and the DFD11B. The number is set with DIP switches S2-PD0 to S2-PD4 in a
binary coded manner.
Configuring the
SBus communi-
cation of the
gateway
The "AS" DIP switch is used to configure the SBus communication of the gateway
(
→
chapter "Auto setup for gateway operation").
The configuration is carried out when the "AS" DIP switch is set from "0" to "1". For fur-
ther operation, the "AS" DIP switch must remain in position "1" (= ON).
NOTE
Before changing a DIP switch setting, disconnect the drive inverter from power (supply
voltage and 24 V backup operation). The DIP switch settings are adopted during ini-
tialization of the driver inverter only.
DIP switch S2
Baud rate
DR1
DR0
0
0
125 kBaud
0
1
250 kBaud
1
0
500 kBaud
1
1
Invalid
[1] Setting the MAC-ID
[2] Setting the baud rate
[3] Setting the process data length
[4] Auto setup for gateway operation
[5] No function
The figure depicts the following settings:
MAC-ID: 4
Baud rate: 125 kBaud
Process data length: 8 PD
62196AXX