This section provides you with information on project planning for the DeviceNet master
and startup of the drive inverter for fieldbus operation.
5.1
Validity of the EDS files for DFD11B
Two different EDS files are available for the configuration of the master (DeviceNet-
Scanner) for the DFD11B:
• if DFD11B is used as a fieldbus option in MOVIDRIVE
®
B, the EDS file
SEW_MOVIDRIVE_DFD11B.eds is required
• if DFD11B is used as a gateway in MOVITRAC
®
B or in the gateway housing
(UOH11B), the EDS file SEW_GATEWAY_DFD11B.eds is required
Install the following files with the RSNetWorx software to build the DeviceNet network
with the DFD11B option: Proceed as follows:
• Select the menu item <Tools/EDS-Wizard> in RSNetWorx. You will be prompted to
enter the names of the EDS and Icon file.
• The files will be installed. For detailed information on the installation of the EDS file,
refer to the Allen Bradley documentation for RSNetWorx.
• After installation, the device is available in the device list under the entry "Ven-
dor/SEW EURODRIVE GmbH".
NOTE
The current version of the EDS file for the DFD11B option card is available on the SEW
homepage (http://www.sew-eurodrive.de) under the heading "Software".
NOTE
Entries in the EDS file must not be changed or expanded. SEW assumes no liability
for inverter malfunctions caused by a modified EDS file!