Manual – DFD11B DeviceNet Fieldbus Interface
29
5
Configuring the MOVIDRIVE® MDX61B drive inverter
Project Planning and Startup
5.3
Configuring the MOVIDRIVE
®
MDX61B drive inverter
The following settings are required for simple fieldbus operation.
However, to control the MOVIDRIVE
®
B drive inverter via DeviceNet, you must first
switch the drive inverter to control signal source (P101) and setpoint source (P100) =
FIELDBUS. The FIELDBUS setting means the drive inverter parameters are set for con-
trol and setpoint entry via DeviceNet. The MOVIDRIVE
®
B drive inverter then responds
to the process output data transmitted by the PLC.
The parameters of the MOVIDRIVE
®
B drive inverter can be set straight away via De-
viceNet without any further settings once the DeviceNet option card has been installed.
For example, all parameters can be set by the PLC after power-on.
Activation of the control signal source and setpoint source FIELDBUS is signaled to the
machine controller using the "Fieldbus mode active" bit in the status word.
For safety reasons, you must also enable the MOVIDRIVE
®
B drive inverter at the ter-
minals for control via the fieldbus system. Therefore, you must wire and program the ter-
minals in such a way that the inverter is enabled via the input terminals. For example,
the simplest way of enabling the drive inverter at the terminals is to connect the DIØØ
(function / CONTROLLER INHIBIT) input terminal to a DC +24 V signal and to program
input terminals DIØ1 ... DIØ7 to NO FUNCTION.