Operating Instructions – Electronic Motor DRC.-..-DAC
143
8
Description of power section parameters
Parameters
8.4.7
Unit functions
Power section parameters \ unit functions \ setup
Factory setting
index 8594.0
Parameter 8594.0 is used to reset the factory settings stored in EEPROM for almost all
parameters.
Setting range:
• 0 = No
• 1 = Standard
• 2 = Delivery status
• 3 = Basic initialization
The following data is not reset when "standard" is selected:
• IPOS program
• Speed control
• Limits
• Serial communication SBus 1
• Speed task 1 / 2
• Error memory
• Statistical data
The "delivery state" setting also resets the data listed above.
Once the data has been reset, parameter 8594.0 automatically reverts to "NO".
Parameter lock
index 8595.0
Setting range: ON / OFF
Setting parameter 8595.0 to "ON" prevents any change to the parameters (except for
index 8617.0 manual reset and the parameter lock itself). This makes sense, for
example, after the drive settings have been optimized. Index 8595.0 must be set to
"OFF" to enable changes to parameters again.
INFORMATION
The parameter lock also acts on the SBus interface and on IPOS
plus®
.
00