172
Operating Instructions – Electronic Motor DRC.-..-DAC
9
Transmitting individual parameters via AS-Interface
Communication with AS-Interface Double Slave GLK31A
The slave replies after the system-related transmission times for parameters.
"Read response OK" response telegram:
Setting ramp t11
down
Set ramp t11 down (parameter
8808.0
) to 0.5 s. The ramp time for ramp t11 down is set
in the same way as the ramp time for ramp t11 up.
Ramp t11 down has index 8808
dec
= 0x2268 and subindex 0.
CTT2 service
MOVILINK
®
protocol
Code
Address
-ing
Manage-
ment
Sub-
index
High
index
Low
index
MSB
data
Data
Data
LSB
data
0x50
0x00
0x32
0x00
0x22
0x67
0x00
0x00
0x00
0x00
Code 0x50 =
Read response OK
Addressing 0x00 =
Addressing the command PCB because this is where the parameter is stored
Management 0x32 =
Write parameter => no MOVILINK
®
error
Subindex 0x00 =
Subindex of the parameter
High index 0x22 =
High value of the index
Low index 0x67 =
Low value of the index
=> Index of parameter = 8807
dec
= 0x2267
hex
The value 0x2267
hex
is written to the bytes high index and low index.
Data MSB 0x00
If the MOVILINK
®
service has been executed correctly, the data byte value is
0x0 = 0
dec
Data 0x00
Data 0x00
Data LSB 0x00