Operating Instructions – Electronic Motor DRC.-..-DAC
123
8
Description of command PCB parameters
Parameters
8.3.2
Setpoints/ramp generators
Command pcb parameters \ setpoints/ramp generators \ setpoint selection
Deactivation of
mechanical control
elements
index 10096.30,
bits 13 – 15
Use this bit-coded selection box to deactivate the mechanical control elements of the
DRC inverter.
The parameter is set at the factory so that all mechanical control elements are effective.
Command pcb parameters \ setpoints/ramp generators \ speed ramps
Ramp t11 up
index 8807.0
Use this parameter to set acceleration ramp "t11 up".
• Unit: [s]
• Setting range: 0 – 1 – 60 s
The ramp times refer to a setpoint step change of
∆
n = 3000 rpm.
In conjunction with AS-Interface double slave GLK31A, the parameter is used to set the
acceleration ramp for function modules 1, 5, 7 of the double slave.
Ramp t11 down
index 8808.0
Use this parameter to set deceleration ramp "t11 down".
• Unit: [s]
• Setting range: 0 – 1 – 60 s
The ramp times refer to a setpoint step change of
∆
n = 3000 rpm.
In conjunction with AS-Interface double slave GLK31A, the parameter is used to set the
deceleration ramp for function modules 1, 5, 7 of the double slave.
Bit
Meaning
Information
13
Deactivation of the setpoint
potentiometer f1
Bit not set:
Setpoint potentiometer f1 active
Bit set:
Setpoint potentiometer f1 not active
Setting the setpoint and the maximum
speed using parameters
14
Deactivating switch f2
Bit not set:
Switch f2 active
Bit set:
Switch f2 not active
Setting the setpoint and the minimum
speed using parameters
15
Deactivating switch t1
Bit not set:
Switch t1 active
Bit set:
Switch t1 not active
Setting the ramp times using parameters
00
I