164
Operating Instructions – Electronic Motor DRC.-..-DAC
9
Transmitting individual parameters via AS-Interface
Communication with AS-Interface Double Slave GLK31A
Deactivating
mechanical control
elements
You have to deactivate the mechanical control elements because the parameters of the
DRC inverter are to be set via AS-Interface. To do so, write the value 65535
dec
=
0xFFFF to parameter
10096.30
.
"Exchange request" service:
When the GLK31A double slave receives the service "Exchange request" 0x1D, it sends
the MOVILINK
®
protocol to the DRC inverter. Once the DRC inverter receives the
MOVILINK
®
response, the GLK31A double slave sends the response "Exchange re-
sponse OK" to the AS-Interface master. This means another "Read request" service of
the AS-Interface master is not required.
The slave replies after the system-related transmission times for parameters.
"Exchange response OK" response telegram:
CTT2 service
MOVILINK
®
protocol
Code Index Read
length
Write
length
Address-
ing
Manage-
ment
Sub-
index
High
index
Low
index
MSB
data
Data Data
LSB
data
0x1D
0x02
0x09
0x09
0x00
0x32
0x1E
0x27
0x70
0x00
0x00 0xFF 0xFF
Code 0x1D =
Exchange request
Index 0x02 =
MOVILINK
®
parameter service
Read length 0x09 =
Length of the MOVILINK
®
response
Write length 0x09 =
Length of the MOVILINK
®
request
Addressing 0x00 =
Addressing the command PCB because this is where the parameter is stored
Management 0x32 =
Write parameter
Subindex 0x1E =
Subindex of the parameter
High index 0x27 =
High value of the index
Low index 0x70 =
Low value of the index
=> Index of the parameter = 10096
dec
= 0x2770
hex
The value 0x2770
hex
is written to the bytes high index and low index.
Data MSB 0x00
The parameter must be set to 65535
dec
= 0xFFFF to deactivate the
mechanical control elements.
This value is written to the 4 data bytes.
Data 0x00
Data 0xFF
Data LSB 0xFF
CTT2 service
MOVILINK
®
protocol
Code
Address-
ing
Manage-
ment
Sub-
index
High
index
Low
index
MSB
data
Data
Data
LSB
data
0x5D
0x00
0x32
0x1E
0x27
0x70
0x00
0x00
0x00
0x00
Code 0x5D =
Exchange request OK
Addressing 0x00 =
Addressing the command PCB because this is where the parameter is stored
Management 0x32 =
Write parameter
Subindex 0x1E =
Subindex of the parameter
High index 0x27 =
High value of the index
Low index 0x70 =
Low value of the index
=> Index of the parameter = 10096
dec
= 0x2770
hex
The value 0x2770
hex
is written to the bytes high index and low index.
Data MSB 0x00
If the MOVILINK
®
service has been executed correctly, the data value is 0
dec
=
0x0
Data 0x00
Data 0x00
Data LSB 0x00